en
Installation and operating instructions • Wilo-Control EC-L • Ed.04/2022-09
45
2.
Open the switchgear.
DANGER! Risk of fatal injury due to electric current! There is a risk of fatal injury
when performing work on the open switchgear! This work must be carried out by a
qualified electrician!
3.
Correct the motor current on the potentiometer with a screwdriver (see Overview of
components [
14]). Read changes directly off the display.
4.
Once all of the motor currents have been corrected, close the switchgear.
▶
Motor current monitoring set. Perform direction of rotation check.
8.5.7
Check the direction of rotation of
the connected pumps
NOTICE
Rotating field, power supply and pump connection
The rotating field is routed from the mains connection directly to the
pump connection. Check the required rotating field of the pumps to be
connected (clockwise or counter-clockwise)! Observe the installation
and operating instructions of the pumps.
Perform a test run to check the direction of rotation of the pumps.
CAUTION! Damage to
property! Perform the test run under the prescribed operating conditions.
✓
The switchgear is closed.
✓
Configuration of menu 5 and menu 1 complete.
✓
All pumps are switched off in menu 3.02 to 3.04: Value is “off”.
✓
The pumps are enabled in menu 3.01: Value is “on”.
1.
Start Easy Actions menu: Turn the operating button 180°.
2.
Select the pump’s manual operation mode: turn the operating button until the menu
item is displayed:
- Pump 1: P1 Hand
- Pump 2: P2 Hand
- Pump 3: P3 Hand
3.
Start test run: Press the operating button. The pump runs until the operating button is
released.
4.
Check direction of rotation.
⇒
Incorrect direction of rotation:
Exchange the two phases on the pump connection.
▶
Direction of rotation checked and corrected as necessary. The initial configuration is
complete.
8.6
Start automatic mode
Automatic mode after initial configuration
✓
The switchgear is closed.
✓
Configuration complete.
✓
Direction of rotation correct.
✓
Motor current monitoring set correctly.
1.
Start Easy Actions menu: Turn the operating button 180°.
2.
Select the pump for automatic mode: Turn the operating button until the menu item is
displayed:
- Pump 1: P1 Auto
- Pump 2: P2 Auto
- Pump 3: P3 Auto
3.
Press the operating button.
⇒
Automatic mode is set for the selected pump. Alternatively, setting can be per-
formed in Menu 3.02 to 3.04.
▶
Automatic mode switched on.
Automatic mode after shutdown
✓
The switchgear is closed.
✓
Checked configuration.
Summary of Contents for Control EC-L
Page 2: ...Control EC L https qr wilo com 1401 ...
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......