en
40
Installation and operating instructions • Wilo-Control EC-L • Ed.04/2022-09
8.5.3
Menu 1: Values for switching on
and off
Fig. 56:
Menu 1.09
Menu no.
1.09
Software version: All
Description
Base-load pump switch-off delay
Value range
0 … 60 s
Factory setting
0 s
Explanation
Time until the base-load pump is switched off after the fill
levels are reached.
Fig. 57:
Menu 1.10
Menu no.
1.10
Software version: All
Description
Peak-load pump activation delay
Value range
0 … 30 s
Factory setting
3 s
Explanation
Time until the peak-load pump is switched on after the fill
levels are reached.
Fig. 58:
Menu 1.11
Menu no.
1.11
Software version: All
Description
Peak-load pump switch-off delay
Value range
0 … 30 s
Factory setting
1 s
Explanation
Time until the peak-load pump is switched off after the fill
levels are reached.
Fig. 59:
Menu 1.12
Menu no.
1.12
Software version: All
Description
Base-load pump On level
Value range
0.06 ... 12.5 m (
NOTICE! The actual value range is dependent
on the setting in menu 5.09.)
Factory setting
0.40 m
Explanation
“Drain” operating mode: Value must be 0.03 m
higher
than the
“Base-load pump Off level” (menu 1.13).
“Fill” operating mode: Value must be 0.03 m
lower
than the
“Base-load pump Off level” (menu 1.13).
NOTICE! The menu item is only visible if the value “Level” or
“Bell” have been set in menu 5.07.
Fig. 60:
Menu 1.13
Menu no.
1.13
Software version: All
Description
Base-load pump Off level
Value range
0.06 ... 12.5 m (
NOTICE! The actual value range is dependent
on the setting in menu 5.09.)
Factory setting
0.23 m
Explanation
“Drain” operating mode: Value must be 0.03 m
lower
than the
“Base-load pump On” level (menu 1.12).
“Fill” operating mode: Value must be 0.03 m
higher
than the
“Base-load pump On level” (menu 1.12).
NOTICE! The menu item is only visible if the value “Level” or
“Bell” have been set in menu 5.07.