Appendix A: Data Sheet
Rated Input Voltage:
106 – 230 V AC, +/- 15% variation allowed
Rated Input Current:
16 A
Sinusoidal:
CE
EN 60555, IEC 555 pow. fact. 0,98 (230VAC)
50/60 Hz
Inrush current:
16 A, cold unit
Output Insulation
(SELV)
CE
EN 60950 , ISO 380, VDE 0805, UL 1950, C22.2.950
DC Output
power with different input voltages at the rated current (16A), calculated with
typical efficiency of 75%
115VAC / 1.380Wnom, 1580Wpeak
230VAC / 2.760W, 3170Wpeak
Regulation fast remote sense circuit (short sensed distance, sense connected to output
at the MARA power bin):
Static:
MDC/M 2-8 V / 30–60
V
< 15 mV
(+/-100% load, +/- full
mains range)
MDC/M other voltages
< 0.05 %
(+/-100% load, +/- full DC
input range)
Dynamic (0.5 m
wire):
MDC/M 2-8 V
< 100 mV
(50 % - 75 % load change)
other
< 0.7 %
(50 % - 75 % load change)
Recovery Time:
MDC/M 2-8V
1%: 0.2 ms
0.1%: 0.5 ms
(50 % - 75 % load change)
MDC/M 5-16V, 7-24V
1%: 0.0 ms
0.1%: 1.0 ms
(50 % - 75 % load change)
MDC/M 30-60V
1%: 0.5 ms
0.1%: 1.0 ms
(50 % - 75 % load change)
Conditions
Current slope <1000A/ms, 20mF per 100A parallel to load
Regulation slow remote sense circuit (long sensed distance)
:
Static:
MDC/M 2-8V/ 30-60V
< 15 mV
(+/-100% load, +/- full
mains range)
Other
< 0.05 %
(+/-100% load, +/- full
mains range)
Dynamic:
Dynamic deviation depends on current slope resp. filter capacitors at
load side only
30m cable to load, 0,3mF capacitance at load side, 1V drop at
nominal load, 10% - 90 % load change with 3ms slope (50A
output= 13,33A/ms) leads to less than 10% temporary output
voltage deviation
Recovery Time (40m
wire, 5V at load side,
U
drop
< 2 V:
MDC 2-7V, 2-8V
10%: <15 ms
1%: <25 ms
(50 % - 75 % load change)
Other
10%: <15 ms (50 % - 75 % load change)
8. June 2010
18