In this situations the advanced (PID) regulator of the
Moderate Regulation
should be used.
If the load is connected with really long or high-inductance cable, the
Slow Regulation
check
box should be checked additionally. This increases the time constant of the I-Regulator.
The
Control and Status
group has buttons to switch the channel on or off. In case of any
errors they are displayed here, too.
The
Supervision
group contains all items which the microcontroller can observe. In case of
exceeding a limit, a dedicated action can be assigned to each item.
It is possible to
●
ignore the failure (not possible at max. terminal voltage, max power and max.
temperature: the power supply has to protect itself)
●
switch this channel off
●
switch all channels with the same group number off
●
switch all channels of the power supply off
The Identification group contains just a single item, the group number of the channel.
Many SNMP network commands can address a single channel (identified by the channel
number) or a group (identified by the group number), so it is possible to access different
channels with only one network message.
3.3.3 Global and Network Configuration Dialog
In the
Network
group box you enter the
TCP/IP network settings (IP address,
subnet mask and default gateway). You
have to use the parameters of your
local network here. Please contact your
network administrator for details.
HTTP and SNMP port numbers should
only modified if you know what you
do. Setting any port to 0 disables the
server.
If the “Channels Switch On with Main
Switch” check box in the
Other
group
box is checked, all output channels are
switched on if the main switch is
switched on.