background image

 

2.  WATER SUPPLY (feed) - Turn off the water supply.  Place the 3/8” brass compression valve 

in the cold-water line.  Attach one end of the 3/8” tubing to the valve using the brass insert and 

nylon sleeve provided and attach the other end to the RO unit filter connection marked 

“FEED”.  See the SYSTEM LAYOUT drawing. 

 

3.  DRAIN LINE (concentrate or reject) - Attach the drain saddle tee to the 1-1/2” outside 

diameter drain pipe.  Drill a 3/8” hole into the pipe.  Insert the 1/2” npt x 3/8” compression 

fitting into the saddle tee.  Attach the 3/8” tube and connect it to the reject fitting.  See the 

system layout drawing. 

 

4.  SERVICE LINE (permeate or product) - Drill a 5/8” hole in the sink top (use a carbon tungsten 

drill bit) and attach the chrome faucet.  Attach the 1/4” outside diameter tubing from the tee 

(marked permeate) to the compression tee on the pressure tank and then to the compression 

nut on the bottom of the faucet.  See the system layout drawing. 

 

5.  ON CHLORINATED WATER - You 

must rinse

 the activated carbon cartridges.  Do this by 

placing a container under the sample port, (see the system layout drawing, item 21) open the 

valve 4 or 5 turns and turn on the water supply.  Continue this procedure until no more black 

color appears in the water. 

 

The unit is factory tested at a 5 to 1 recovery ratio.  Rejection of the TDS (Total Dissolved Solids) is at 

least 90% at 185 PSI, 78° F and 1000 PPM TDS. 

 

NOTE:  If the RO pump pressure exceeds 190 PSI: 

1.  Remove the acorn nut on the right side of the pump 
2.  Using a common screwdriver, turn the slotted screw counter-clockwise to decrease pressure. 
3.  Replace the acorn nut. 

 

WARNING: PUMP WARRANTY IS VOIDED IF THE PRESSURE EXCEEDS 190 PSI 

 

NOTE:

 Pump model units will automatically shut down when the pressure in the holding tank reaches 40 

PSI.  Back pressure on the holding tank should not exceed 40 PSI. The RO pump will start automatically 

when the product pressure drops below 20 PSI. 

 

V  OPERATION 

 

NOTE:

  On new installations, do not allow any product water to flow into the storage tank until the RO unit 

has run for one hour and is thoroughly flushed.  This will insure the removal of all traces of the 

preservative from the membranes.  Do this by shutting down the storage tank valve and opening up the 

faucet and let the water run into the drain.  Be sure to re-open the storage tank valve for normal operation. 

1.  After all water hook-ups are complete, turn the water supply on and check for leaks. 
2.  To start the RO unit, plug in the RO unit using the 3 prong plug in a standard 115 volt outlet or 

220 volts if designated for 220 volt power. 

3.  The unit will not operate unless the feedwater pressure is 20 PSI or higher. 
4.  The system is equipped with a preset reject water flow controller.  No adjustments are 

required for setting flow rates. 

 

Summary of Contents for CAK Series

Page 1: ...C Ca ak k N Na ak k W Wa at te er r P Pu ur ri if fi ic ca at ti io on n S Sy ys st te em m REMOVE 90 TO 98 OF THE TOTAL DISSOLVED SOLIDS AND 100 OF PARTICULATE CONTAMINANTS...

Page 2: ...s manual be read and understood before performing installation operation and maintenance of the system The equipment warranty may be voided if instructions are not followed correctly The information p...

Page 3: ...s Pressurized Water Hazardous Chemicals Noise Failure to follow good safety practices and the instructions included in this manual may result in damage to the unit its surroundings personal injury or...

Page 4: ...ll out the operator s log sheet completely and return to XYLEM WET to validate warranty NOTE Hardness and iron will foul the membranes and result in a decrease in the amount and quality of the water p...

Page 5: ...ced Clogged inlet filters As pre filters age and collect debris the pressure drop across the filter increases and flow decreases At some point the reduced pressure or flow may actually cause the syste...

Page 6: ...tio Rejection of the TDS Total Dissolved Solids is at least 90 at 185 PSI 78 F and 1000 PPM TDS NOTE If the RO pump pressure exceeds 190 PSI 1 Remove the acorn nut on the right side of the pump 2 Usin...

Page 7: ...poly fitting Put them aside and keep them as spares 7 Connect the P6UC4 Poly fitting to the ends of the each of the tubing connections removed step 3 The tubing connections are long enough to bend to...

Page 8: ...y done with the sample port See the SYSTEM LAYOUT drawing NOTE Higher levels of chlorine may require a larger carbon prefilter if one is needed contact your local sales representative 3 RO PUMP once e...

Page 9: ...eat build up can also cause leaks to develop and will cause fouling of the membranes VENTILATION Inadequate ventilation will cause the pump motor to overheat and cut out It will also cause leaks due t...

Page 10: ...change in water production is approximately 2 Thus if the water temperature is 5 degrees C the amount of water produced will be 40 less than at 25 degrees C TDS AND REJECTION RATE As the TDS total di...

Page 11: ...drain the water from the RO membrane assembly and plug the holes before shipping NOTE 2 For the most accurate TDS readings let the RO unit run for at least 15 minutes NOTE 3 For the warranty to be va...

Page 12: ...12...

Page 13: ...13 Part Number 07 MS 1020 Rev 3 October 2018...

Reviews: