background image

 

I  INITIAL INSPECTION AND HANDLING 

 

On receipt of the unit, note any damage on appropriate shipping documents.  File damage claims with the 

carrier immediately and NOT with XYLEM WET. 

 

II  QUALITY CONTROL 

 

Each RO unit is tested and preserved before shipment to insure quality and performance.  This 

preservative must be flushed completely from the unit.   See the 

OPERATION

 section of this manual for 

the procedures to do so. 

 

III  ELECTRICITY 

 

The CAK-139 and NAK-139 BP require 115 volts, 60 Hz, single phase power.  The service line should 

have a 15 AMP capacity. 

 

NOTE:

  220 volt, 50 and 60 Hz units are available as options, motors used on these models are dual 

voltage and dual cycle.  To verify the electrical specifications, check the “Manufactured By” plate and NOT 

the motor plate! 

 

IV  INSTALLATION 

 

NOTE:

  For long term performance with minimum maintenance, check for the following: 

 

1.  That ALL chlorine is removed from the feedwater 

2.  Hardness is removed from the feedwater 

3.  Iron is removed from the feedwater 

4.  Fill out the operator’s log sheet completely and return to XYLEM WET to validate warranty. 

 

NOTE:

 Hardness and iron will foul the membranes and result in a decrease in the amount and quality of 

the water produced.  The membrane’s performance can be restored by a cleaning procedure (contact 

your local representative). 

NOTE:

  If a water softener is used, it should be set to regenerate at night or when the RO unit is not 

running. 

WARNING:

  Chlorine must be removed from the feedwater if present.  Chlorine will damage the TFC 

membrane and VOID THE WARRANTY.  If activated carbon is used to remove chlorine, the carbon 

MUST be thoroughly rinsed to remove any small carbon fines before the RO unit is operated. 

WARNING:

 If this pump driven reverse osmosis system is not installed and maintained according to all 

the instructions provided by the manufacturer, and as a result of not following these instructions by the 

installer, the water temperature is allowed to exceed 95 degrees F (35 degrees C), then any consequential 

damages that result from components on the equipment failing due to any resulting heat stress are not the 

responsibility of the manufacturer and are not covered under the manufacturer’s warranty. 

Summary of Contents for CAK Series

Page 1: ...C Ca ak k N Na ak k W Wa at te er r P Pu ur ri if fi ic ca at ti io on n S Sy ys st te em m REMOVE 90 TO 98 OF THE TOTAL DISSOLVED SOLIDS AND 100 OF PARTICULATE CONTAMINANTS...

Page 2: ...s manual be read and understood before performing installation operation and maintenance of the system The equipment warranty may be voided if instructions are not followed correctly The information p...

Page 3: ...s Pressurized Water Hazardous Chemicals Noise Failure to follow good safety practices and the instructions included in this manual may result in damage to the unit its surroundings personal injury or...

Page 4: ...ll out the operator s log sheet completely and return to XYLEM WET to validate warranty NOTE Hardness and iron will foul the membranes and result in a decrease in the amount and quality of the water p...

Page 5: ...ced Clogged inlet filters As pre filters age and collect debris the pressure drop across the filter increases and flow decreases At some point the reduced pressure or flow may actually cause the syste...

Page 6: ...tio Rejection of the TDS Total Dissolved Solids is at least 90 at 185 PSI 78 F and 1000 PPM TDS NOTE If the RO pump pressure exceeds 190 PSI 1 Remove the acorn nut on the right side of the pump 2 Usin...

Page 7: ...poly fitting Put them aside and keep them as spares 7 Connect the P6UC4 Poly fitting to the ends of the each of the tubing connections removed step 3 The tubing connections are long enough to bend to...

Page 8: ...y done with the sample port See the SYSTEM LAYOUT drawing NOTE Higher levels of chlorine may require a larger carbon prefilter if one is needed contact your local sales representative 3 RO PUMP once e...

Page 9: ...eat build up can also cause leaks to develop and will cause fouling of the membranes VENTILATION Inadequate ventilation will cause the pump motor to overheat and cut out It will also cause leaks due t...

Page 10: ...change in water production is approximately 2 Thus if the water temperature is 5 degrees C the amount of water produced will be 40 less than at 25 degrees C TDS AND REJECTION RATE As the TDS total di...

Page 11: ...drain the water from the RO membrane assembly and plug the holes before shipping NOTE 2 For the most accurate TDS readings let the RO unit run for at least 15 minutes NOTE 3 For the warranty to be va...

Page 12: ...12...

Page 13: ...13 Part Number 07 MS 1020 Rev 3 October 2018...

Reviews: