Programming
24
Soft Start Period
+
Fast Running Period
+
Soft Stop Period
=
Total Run Time
Fast Running Period
=
Total Run Time
–
Soft Start Period
–
Soft Stop Period
15 seconds
=
23 seconds
–
3 seconds
–
5 seconds
Factory default setting for the Fast Running Period is 15 seconds. Please
consider the below calculation example. When the Soft Start Period is set at 3
seconds and the Total Run Time is 23 seconds, the Fast Running Period has to
be adjusted to 15 seconds in order to meet the Soft Stop Period of 5 seconds.
Adjust in the
Menu
Pb
3
seconds
Adjust in the
Menu
PC
15
seconds
This will result to
a Soft Stop Period
of 5 seconds
This will result to
a Total Run Time
of 23 seconds
1.
The Fast Running Period can be adjusted by pressing the
INC
or
DEC
buttons.
2.
Press the button
FUNC
in order to store the setting.
The display shows
Pd
.
3.
Press the button
FUNC
once more in order to quit the menu and to save the
setting.
The display shows
“
– –
“.