15

4.4.8. Valid time of loop detector signal

In the process of opening or up limit position, the duration time of the loop detector
signal needs to exceed the setting time, and the auto-closing action will be executed
after the loop detector signal disappears, avoiding that the loop detector signal is too
short and triggers the auto-closing action to hit the vehicles. The default time is
200ms. Range: 100ms-900ms.

4.4.9. Beep of Loop detector signal

There is loop detector signal (there is vehicle on the loop wire) when boom is at up
limit position, the buzzer will emit a hint tone. "ON" has a sound, and "OFF" has no
sound. “ON” is default.

4.4.10. Failure angle of loop detector anti-smashing

During the closing process, when the boom arrives at the setting angle from the
horizontal level, it will not respond to the signal of loop detector, to prevent vehicle
from being followed by other vehicles, and can also prevent the misoperation of the
loop detector from triggering the opening of the barrier gate. The default value is 5
degrees.

4.4.11. Failure angle on obstacle

During the closing process, when the boom arrives at the setting angle from the
horizontal level, if the boom meets on obstacle, it will not respond to barrier gate
opening. The default value is 10 degrees.

4.4.12. Switching angle of R&G light

When the boom opens to the setting angle, the relay of R&G light will close. The
default value is 60 degrees.

4.4.13. Wire control signal type measurement

"Infrared photocell", "loop detector/radar” and "stop" signals of the wire control
interface can be set to normal open input and normal close input, and the default is
normal open input.

4.5. Controller Parameter Setting of Slave Motor

Long press “

” button for 2 seconds to enter the regular menu setting status. The

LED digital tube will display “F-XX”. Select menu items by short press or long press

Summary of Contents for DC24V

Page 1: ...I DC Variable Frequency 3D Barrier Gate SCB02 DC24V Manual V1 0 1...

Page 2: ...ead this manual carefully before using the equipment and strictly follow it during use Please keep the manual properly after reading Operating Environment Requirements Please transport use and store t...

Page 3: ...anations 4 4 2 Controller Parameter Setting of Master Motor 6 4 3 Regular Menu Command List of Master Motor 6 4 4 Advanced Menu Command List of Master Motor 12 4 5 Controller Parameter Setting of Slav...

Page 4: ...le to stop at any position in three dimensional space no longer limited height problem 1 1 7 Double protection one drive failure will not affect the other drive and the barrier gate can still operate...

Page 5: ...4 Motor power up and down power 180W horizontal power 60W 1 2 5 Relative Humidity 30 80 No condensation 1 2 6 Distance of remote control L 30M 1 2 7 Running Speed 0 3 seconds MAX 1 2 8 MTBF 8 000 000...

Page 6: ...on the ground with 4 sets M16 150 expansion bolts At the location where the cabinet is installed the barrier foundation should be made according to the site conditions and the cast in place foundatio...

Page 7: ...tem Explanation Wire Control Interface This interface is available for parking system also available for external controller to control barrier gate UP Short circuit UP and GND Down Short circuit Down...

Page 8: ...modes via option 4 of the advanced menu DC12V Power Output Provide 1A current output available for radar or small light strips Interface for R G lights Available to connect with R G lights to indicate...

Page 9: ...used to display the information of the slave motor of the barrier gate such as the working status parameters menu items 4 2 Controller Parameter Setting of Master Motor Long press button for 2 second...

Page 10: ...he angle at which the boom enters a low speed area in the opening process if the boom shakes after it is opened in place users can reduce this value 1 5 End Speed 8 1 50 6 8 The minimum speed at which...

Page 11: ...ter it is closed in place users can increase this value 2 4 Angle of Low speed Area 0 0 45 0 The angle at which the boom enters a low speed area in the closing process if the boom shakes after it is c...

Page 12: ...ed that chapter 1 5 set until it is opened in place If the value is 90 the function is invalid If the boom shakes after it is opened in place users can reduce this value appropriately Chapter 2 4 has...

Page 13: ...when the barrier gate is installed under an eaves please select the Find down limit only mode 4 2 Manual learning f up and down Limit None operate according to the prompts on the screen In manual mod...

Page 14: ...clear code Press the Setting button to invert the color of the symbol on the screen and press and at the same time to clear the code of all remote controllers 4 3 6 RS485 setting Sub menu Defaults Ran...

Page 15: ...e sensitivity is the smaller it is the higher the sensitivity Unit millisecond 4 3 10 Restore factory defaults press the setting button to invert the color of the symbol on the screen and press and at...

Page 16: ...ier gate closes at down limit position users can increase this value appropriately to get some force 3 2 Motor type 129 Rotates Forward 129 Forward Reverse CB03 Forward Reverse It is used for matching...

Page 17: ...sed when boom falls down the signal during boom falling down and boom at down limit position can be used as R G light signal or used for detecting the barrier gate running status 4 4 5 Buffer time for...

Page 18: ...op detector to prevent vehicle from being followed by other vehicles and can also prevent the misoperation of the loop detector from triggering the opening of the barrier gate The default value is 5 d...

Page 19: ...r the boom up speed F 01 Boom Down Speed 100 15 100 90 100 The smaller the value the faster the boom down speed F 02 Boom Up deceleration position 40 10 80 35 45 The angle at which the boom up starts...

Page 20: ...xplanation F 02 Boom up deceleration position It is used to set the starting position of deceleration in the process of boom lifting up The unit of angle is 0 degrees when the barrier gate is in the h...

Page 21: ...s speed when boom lifts up If the parameter is set too large the gate lever will shake when it is opened F 07 End speed of boom down The speed for boom moves to down limit The boom will end moving at...

Page 22: ...te control learning This item is used for the remote control learning of the 3 wire radio receiver of the slave motor It is only used when the main motor fails and the slave motor is used to control t...

Page 23: ...misoperation it needs to set a specific value before pressing button to complete the operation 5 Clear all learned remote controller of the 3 wire radio receiver of the slave motor 10 Restore factory...

Page 24: ...ined by F 07 the larger the value the greater the force And the value needs to be set properly and the boom can be closed to limit position without swinging is ok Set the pressure of the boom holder o...

Page 25: ...s a lot at up limit position Opening speed in up limit position is relatively large Reduce the value of 1 5 in regular menu of the main motor Opening deceleration angle is large Reduce the value of 1...

Page 26: ...The closing deceleration angle of the slave motor F 03 is too small Increase the value of F 03 Boom down limit position speed of the slave motor F 07 is too large Reduce the value of F 07 6 Warranty a...

Page 27: ...t 7 4 Remote control distance will be shortened or not work in cases like big object screening battery exhausting extreme weathers 8 Packing List Name Specification Quantity Unit Application Screw Nut...

Reviews: