Installation and operating instruction
Oil burner WL40Z-A 1LN
7 Commissioning
83298902 2/2019-05 La
43-112
Set pump pressure for stage 2
The pump pressure must be set according to the nozzle selected [ch. 4.2].
Check pump pressure at pressure gauge.
Set pressure using pressure regulating screw
1
:
increase pressure: clockwise rotation,
decrease pressure: anticlockwise rotation.
1
Adjust P
9
Check combustion values
Determine combustion limit [ch. 7.5].
Set excess air via air damper setting [L/A].
Adjust P
1
Press [-] key.
Burner drives to stage 1 (P
1
).
Check combustion values
Determine combustion limit [ch. 7.5].
Set excess air via air damper setting [L/A].