Installation and operating instruction
Oil burner WL40Z-A 1LN
10 Troubleshooting
83298902 2/2019-05 La
85-112
10.3 Operating problems
The following faults must only be rectified by qualified personnel:
Observation
Cause
Rectification
Poor start behaviour of burner
Mixing pressure too high
Correct mixing pressure in ignition
load, if necessary set P
0
different to
P
1
Ignition electrodes set incorrectly
Set ignition electrodes [ch. 9.6]
Mixing head set incorrectly
Set mixing head [ch. 9.8]
Oil pump makes severe mech-
anical noise
Oil pump sucks air
Ensure oil supply is tight
Suction resistance in oil line too high
Clean filter
Check oil supply
Oil nozzle atomisation uneven
Nozzle blocked/soiled
Replace nozzle [ch. 9.4]
Nozzle worn
Flame tube/diffuser has heavy
soot deposit
Oil nozzle defective
Replace nozzle [ch. 9.4]
Mixing head set incorrectly
Set mixing head [ch. 9.8]
Incorrect combustion air quantity
Adjust burner
Boiler room ventilated insufficient
Ensure sufficient boiler room ventila-
tion
Wrong oil nozzle
Check nozzle type [ch. 4.2]
Combustion pulsating or burner
booming
Mixing head set incorrectly
Set mixing head [ch. 9.8]
Incorrect combustion air quantity
Adjust burner
Wrong oil nozzle
Check nozzle type [ch. 4.2]
CO content too high
Nozzle distance too big
Check nozzle distance, adjust if
necessary [ch. 9.8]
Stability problems
Nozzle distance incorrect
Check nozzle distance, adjust if
necessary [ch. 9.8]
Wrong oil nozzle
Check nozzle type [ch. 4.2]
No display at operating panel
Plug from operating panel not properly
plugged in
Plug in plug on combustion manager
correctly
Operating panel defective
Replace operating panel