Installation and operating instruction
Oil burner WL40Z-A 1LN
9 Servicing
83298902 2/2019-05 La
75-112
Press [+].
Setting level (parameter
E0
) is displayed.
Adopt value
0
(single fuel burner), if necessary adjust using [ENTER] and [-] key.
Press [+].
E1
is displayed.
The value of parameter E1 can not be altered.
0
: intermittent operation (Standard)
1
: continuous operation
Press [+].
E2
is displayed.
Set value
2
(flame sensor QRB4 or flame sensor for continuous operation) using
[Enter] and [+] key.
Press [+].
E3
is displayed.
If required, set value using [ENTER] and [+] keys.
1
(fan control): burner without variable speed drive
3
(variable speed drive): burner with variable speed drive
Press [+].
E4
is displayed.
Adopt value
0
(no ignition delay), if necessary set using [Enter] and [-].
Press [+].
Combustion manager changes into the setting level for step points.