Installation and operating instruction
Oil burner WL40Z-A 1LN
7 Commissioning
83298902 2/2019-05 La
57-112
7.6 Subsequent optimisation of operating points
If necessary, the combustion values can subsequently be corrected.
Unplug bridging plug No. 7 on combustion manager.
Combustion manager drives to Standby.
Briefly press [–] and [+] simultaneously.
Combustion manager changes to access level.
Press [+].
Combustion manager changes to setting level.
Plug in bridging plug No. 7 on combustion manager.
Burner starts and stops in operating point P
0
(ignition position).
Initiate the other operating points using the [+] or [-] key and optimise if required.
Exit setting level
Press [G] and [L/A] simultaneously.
The combustion manager changes to operating level.