Installation and operating instruction
Oil burner WL40Z-A 1LN
4 Installation
83298902 2/2019-05 La
21-112
Nozzle selection table
Different load values are possible due to tolerances.
Stage 1
Burner capacity [kW] at pump pressure
Nozzle size [gph]
10 bar
11 bar
12 bar
2.50
–
119
124
2.75
124
131
136
3.00
136
143
149
3.50
158
165
174
4.00
181
189
199
4.50
204
213
223
5.00
226
237
248
5.50
249
261
272
Stage 2
Burner capacity [kW] at pump pressure
Nozzle size [gph]
20 bar
22 bar
24 bar
2.50
160
169
176
2.75
175
183
190
3.00
192
201
211
3.50
224
234
245
4.00
256
267
280
4.50
287
301
314
5.00
320
336
351
5.50
351
368
–
Conversion of burner capacity to oil throughput see formula below.
Oil throughput in kg/h =
Burner capacity in kW
11.9 kWh/kg