Troubleshooting
(continued)
Excessive domestic water temperature
1 Adjust WM97+ control settings and check operation.
s
Follow instructions in the boiler manual and this manual to adjust tank temperature
and boiler water temperature.
s
If controls are set properly, check tank sensor installation and operation.
s
See the illustration at right for locations of the sensor wells. The lower well is on the
side opposite the DHW connections. (This illustration shows a right-oriented tank.)
s
Check whether sensors are inserted completely into their wells. If not, press in firmly
and recheck Aqua Logic (CWH) operation.
s
If sensors are properly inserted in their wells, disconnect each sensor harness and
attach an ohmmeter. The table below shows the correct values for the sensor at
various temperatures.
Temp
(°F)
Sensor ohms
Temp
(°F)
Sensor ohms
Temp
(°F)
Sensor ohms
Min
Max
Min
Max
Min
Max
34265
37871
8504
9399
2517
2782
27834
30764
6847
7568
2091
2311
21630
23907
5545
6129
1744
1928
16944
18727
4517
4992
1461
1615
13372
14780
3698
4088
1229
1359
10629
11747
3043
3364
1038
1147
s
Use the resistance values at 32°F, 60°F, 70°F and 212°F to
measure the sensor resistance at known temperatures
(ice point, room temperature and sea level boiling
point). For ice point and boiling point, insert the sen-
sor in water at that temperature. Use an ohmmeter to
read resistance value. To check whether the WM97+
control is correctly sensing temperature, you can use
a resistance decade box. Connect the decade box tem-
porarily in place of a sensor and read the correspond-
ing temperature on the WM97+ control display. The
temperature should be close to the value corresponding
to the input resistance.
2 Recirculation loop needed?
s
Installing a properly-sized recirculation loop will not
only provide prompt delivery of hot water, but it will
provide circulation and mixing of the water within
the tank.
3 Thermostatic mixing valve set too high?
s
Follow instructions in the mixing valve manual to
check mixing valve setting temperate. Adjust if neces-
sary following the manual’s specified procedure.
4 No thermostatic mixing valve installed or mixing valve is defective?
)&4(% -)8).' 6!,6% )3 ./4 ).34!,,%$
$)3#/.4).5%53%/&4(%!QUA,OGIC#7(
!.$).34!,,4(%-)8).'6!,6%&/,,/7).'
).3425#4)/.3 ).4()3 -!.5!, !.$4(%
-)8).'6!,6%-!.5!,
s
The Aqua Logic (CWH)
MUSTNOT
be operated without
a mixing valve installed per the instructions in this
manual and the mixing valve manual.
s
Follow instructions in the mixing valve manual to
check valve operation. If valve is correctly installed and
does not operate correctly, replace the mixing valve.