COMPANION
WATER
HEATER
—
Product Manual
Troubleshooting
(continued)
5 Check for air in the system
s
An air-bound water heater or boiler will not circulate system water properly, resulting in a lack of heat
transfer.
s
Air can be trapped in piping loop sections, the tank coil or the flexible water lines between the boiler and
Aqua Logic (CWH).
s
Connect a drainage hose to the boiler supply piping purge valve (shown in WM97+ manual suggested
piping).
s
Close the WM97+ internal by-pass valve (be sure to return to normal position after purging).
s
Allow water to flow into the boiler return line from the make-up water connection to the system.
s
Allow water to flow until air bubbles no longer appear in the discharge from the drainage hose.
s
Remove drainage hose and return by-pass valve to the normal position.
6 Clean the boiler water system.
s
A dirty boiler system can cause deposits to form on the water heater coil. This insulates the coil, reducing
the heat transfer.
s
Clean the boiler system per the boiler manufacturer’s instructions.
s
Install a strainer in the boiler piping on older installations or for systems likely to carry sediment.
7 Check tank temperature setting
s
Follow directions in this manual to navigate to the tank temperature setting menu.
s
Increase the setting if necessary.
s
Also check the operating mode. Change mode to “High-max performance” if water heater is set to another
mode.
8 Check DHW circulator speed
s
The Aqua Logic (CWH) is supplied with a 3-speed circulator. The speed switch on the circulator must
be set to:
s
3PEED
for WM97+70 or 110 boilers.
s
3PEED
for WM97+155 boilers.
Insufficient hot water
(continued)
Part number 635-500-156/1113