Minimum distances with vertical installation
1.18"
30 mm
10
mm
0.39"
Minimum distance to switch cabinet door (with/without swivel marker)
Calculation of space requirements
The space requirements for a u-control station with n mod-
ules (
horizontal installation
) is calculated as follows:
D
W
Height: 120 mm (4.72
”)
+ 2
x
40 mm (1.57
”)
distances at top and bottom
=
200 mm (7.87”)
Width: 8 mm
(1.57
” )
end bracket
+ 52 mm (2.05”)
controller
+ n
x
11.5 mm (0.45”)
n modules
+ 11.5 mm
(0.45
”)
end plate and end bracket
+ 2
x
20 mm (0.79”)
distances to the sides
=
111.5 mm (4.39”) + n
x
11.5 mm (0.45”)
For
vertical installation
interchange height and width.
When calculating the width, 4.5 mm for the must be added
for the end bracket MEW 35/1 (Order No. 1805610000).
Installation sequence
A u-control station may only be installed in this sequence
(starting from the left/bottom):
–
End bracket
–
Controller
–
Up to 64 active modules
–
End plate and end bracket
If the station has already been configured, please proceed to
the corresponding installation drawing. If you are configuring
the station yourself, please observe the following instruc-
tions:
–
Observe the maximum current carrying capacity (see sec-
tion 4.6)!
–
Furthermore, the modules may be arranged in any
sequence. In order to configure the station as clearly as
possible, we recommend arranging the modules accord-
ing to their function.
Arrangement of safe power-feed modules
A safe power-feed module (PF-O-xDI-SIL) can be positioned
anywhere in the u-control station. All of the following output
modules up to the next PF-O module will be safely discon-
nected (safety segment). Multiple safe power-feed modules/
safety segments can be set up in a single station.
When using u-remote safe power-feed modules,
please also observe the
Modules for Function-
al Safety Manual
.
The manual is available to download from the
Weidmüller website.
Preparation and the required tool
The DIN rail must already be installed. To mechanically install
the u-control station, you will need a 3-mm screwdriver.
▶
Lay out the modules in the intended sequence.
▶
Check whether the DIN rail feet can be moved on both
end brackets. If necessary, loosen the mounting screw
until the DIN rail feet can be moved freely.
▶
If not done yet, fit an earth terminal to the DIN rail.
6 Installation
| Preparations for assembly
41
Manual u-control
2604080000/03/08.2020
Summary of Contents for 1334950000
Page 8: ...8 2604080000 03 08 2020 Manual u control...
Page 22: ...22 2604080000 03 08 2020 Manual u control...
Page 58: ...58 2604080000 03 08 2020 Manual u control...
Page 62: ...62 2604080000 03 08 2020 Manual u control...
Page 70: ...70 2604080000 03 08 2020 Manual u control...
Page 72: ...72 2604080000 03 08 2020 Manual u control...