| Example calculation for the power supply
Example calculation for the current demand (all current values in A)
Module
no.
Product
I
SYS
I
IN
I
OUT
I
S
I
L
Simultaneity
factor
g
Cumulative
current demand
of the input cur-
rent path
Cumulative
current demand
of the controller
output power
path
Cumulative cur-
rent demand of
the PF-O output
power path
UC20-WL2000-AC
0.116
0.116
0
1
UR20-4DI-P
0.008
0.012
0.06
1
0.196
0
2
UR20-4DI-P
0.008
0.012
0.06
1
0.276
0
3
UR20-4DI-P
0.008
0.012
0.12
1
0.416
0
4
UR20-4DI-P
0.008
0.012
0.18
1
0.616
0
5
UR20-8DO-P
0.008
0.015
2
0.5
0.624
1.015
6
UR20-8DO-P
0.008
0.015
4
0.5
0.632
3.03
7
UR20-8DO-P
0.008
0.015
3
0.5
0.64
4.545
8
UR20-8DO-P
0.008
0.015
2
0.5
0.648
5.56
9
UR20-8DO-P
0.008
0.015
1.2
0.5
0.656
6.175
10
UR20-8DO-P
0.008
0.015
4
0.5
0.664
8.19
UR20-PF-O
11
UR20-8DO-P
0.008
0.015
4
0.5
0.672
2.015
12
UR20-8DO-P
0.008
0.015
4
0.5
0.68
4.030
I
SYS
Current consumption from the system power supply
I
IN
Power consumption from input current path
I
OUT
Power consumption from output current path
I
S
Current demand of the connected sensors
I
L
Current demand of the connected actuators
The current demand is just under 10 A! The output
current path must therefore be refreshed
before the
11th module
.
10 A is supplied by the UR20-PF-O module. The
1.81 A calculated as remaining after the 10th module
must
not
be added to the 10 A after the UR20-PF-O
module!
Summary of Contents for 1334950000
Page 8: ...8 2604080000 03 08 2020 Manual u control...
Page 22: ...22 2604080000 03 08 2020 Manual u control...
Page 58: ...58 2604080000 03 08 2020 Manual u control...
Page 62: ...62 2604080000 03 08 2020 Manual u control...
Page 70: ...70 2604080000 03 08 2020 Manual u control...
Page 72: ...72 2604080000 03 08 2020 Manual u control...