| Current demand and power supply
4.6 Current demand and power supply
The u-control controllers use three internal current paths:
The
I
SYS
system current path
supplies the communication
part of the I/O modules; it is fed from the controller input
supply and cannot be interrupted by any module. The maxi-
mum current-carrying capacity of I
SYS
allows a u-control sta-
tion to be expanded with a maximum of 64 active modules
without having to refresh the power.
The
I
IN
input current path
supplies the input circuit of the
input modules as well as the connected I
S
sensors. The cur-
rent must be refreshed with UR20-PF-I (power feed in) mod
-
ules as required. These UR20-PF-I modules isolate the input
current path towards the left (towards the controller), and as
a result start a new electricity segment towards the right.
The
I
OUT
output current path
supplies the output circuit
of the output modules with power, as well as the connect-
ed I
L
actuators. The current must be refreshed with the
UR20-PF-O (power feed-out), as required. These UR20-PF-O
modules isolate the output current path to the left (towards
the controller), and as a result start a new electricity segment
to the right.
The design of the power supply being used must
take start-up peaks into account.
Power supply derating
The power supply is restricted according to the temperature.
The following values apply for the horizontal and vertical po-
sitioning of the u-remote station:
Temperature-dependent values for the power supply
horizontal
vertical
Controller power
supply
55 °C / 2 x 5 A
50 °C / 2 x 5 A
Power-feed mod-
ule power supply
55 °C / 1 x 10 A
50 °C / 1 x 10 A
ATTENTION
Equipment may become damaged if improperly rat-
ed circuit protection is used!
▶
In order to achieve spezification according to UL 248-14
use a UL-approved Type-B automatic circuit breaker
(e. g. ABB Typ S201-B16) or use a fuse
with a maxi-
mum of 10 A protection (e. g. ESKA Art. Nr. 522.227).
ATTENTION
Equipment may become damaged by overcurrent!
▶
Auxiliary supplies as well as signal inputs and outputs
may not be used for supplying the station.
Current demand
Product
I
SYS
I
IN
I
OUT
UC20-WL2000-AC
< 116 mA
–
UC20-WL2000-IOT
< 116 mA
–
UC20-SL2000-EC
< 116 mA
–
UC20-SL2000-EC-CAN
< 116 mA
–
The current demand of the u-remote I/O-modules
can be found in the
Remote-I/O-System
u-remote Manual
.
All manuals are available to download from the
Voltage interruption
The controllers meet severity level PS1 (maximum inter-
ruption time 1 ms) according to IEC 61131-2. If you want
to achieve severity level PS2 (maximum interruption time
10 ms), you must use a power supply that meets the require
-
ments of severity level PS2.
Summary of Contents for 1334950000
Page 8: ...8 2604080000 03 08 2020 Manual u control...
Page 22: ...22 2604080000 03 08 2020 Manual u control...
Page 58: ...58 2604080000 03 08 2020 Manual u control...
Page 62: ...62 2604080000 03 08 2020 Manual u control...
Page 70: ...70 2604080000 03 08 2020 Manual u control...
Page 72: ...72 2604080000 03 08 2020 Manual u control...