4 Configuration
| Use in a potentially explosive atmosphere
17
Manual u-control
2604080000/03/08.2020
4.4 Use in a potentially explosive atmosphere
Please regard the safety notes in section 2.3.
If the u-remote station is used in a potentially explosive
atmosphere rated as Zone 2, the housing must meet the re
-
quirements of explosion protection type Ex n or Ex e and pro
-
tection class IP54. Sensors and actuators that are located in
Zone 2 or in a safe zone can be connected. All cable glands
on the housing must be approved for Ex e.
IP54
Zone 2
safe area
no ex-approval
u-remote
II 3G Ex nA
II 3G Ex nA nC
Use in a potentially explosive atmosphere
ATEX marking (internal certification)
II 3 G Ex nA IIC T4 Gc
WI 13ATEX0002 X
Ta: -20 °C … +60 °C
ATEX marking (external certification)
II 3 G Ex nA IIC T4 Gc
DEMKO 15ATEX1525 X
Ta: -20 °C … +60 °C
II 3 G Ex nA nC IIC T4 Gc (relay modules)
DEMKO 15ATEX1525 X
Ta: -20 °C … +60 °C
IECEx marking
Ex nA IIC T4 Gc
IECEx ULD 15.0013X
Ex nA nC IIC T4 Gc (relay modules)
IECEx ULD 15.0013X
Calculation of power loss for the use in a potentially explo-
sive atmosphere
You will find the module specific data needed for calculation
in the document "WI13ATEX0002_Power_Calc.pdf" which
you can download from the Weidmüller website.
4.5 “PUSH IN” system cabling
Controllers are equipped with the “PUSH IN” connector sys-
tem. Single-strand and fine-strand lines with wire-end ferrules
can be inserted without the need for a tool. Copper wires
with a cross-section measuring between 0.14 mm
2
and
1.5 mm
2
can be connected.
We recommend using the following wire-end ferrules:
Cross-section
AWG
Weidmüller order no.
Weidmüller colour code
Weidmüller order no.
DIN colour code
0.14 mm²
26
9028240000
0.25 mm²
24
9025760000
0.34 mm²
22
9025770000
0.50 mm²
20
9025870000
9019020000
0.75 mm²
18
9025860000
9019050000
1.00 mm²
17
9025950000
9019100000
1.50 mm²
16
0635100000
9019130000
Wire-end ferrules for the wiring
The external dimensions of the crimped wire-end ferrules
must conform with IEC-60947-1. For crimping, we recom-
mend crimp shape A and the following tools:
–
Crimping tool for wire-end ferrules from 0.25 mm² to
1.5 mm² (AWG 24 to 16) with a trapezoidal indentation
crimp, type: PZ 6/5 ZERT (Order No. 9017900000)
–
Crimping tool for wire-end ferrules from 0.14 mm² to
0.75 mm² (AWG 26 to 18)
with a trapezoidal crimp, type:
PZ 1.5 ZERT (Order No. 9017310000)
Summary of Contents for 1334950000
Page 8: ...8 2604080000 03 08 2020 Manual u control...
Page 22: ...22 2604080000 03 08 2020 Manual u control...
Page 58: ...58 2604080000 03 08 2020 Manual u control...
Page 62: ...62 2604080000 03 08 2020 Manual u control...
Page 70: ...70 2604080000 03 08 2020 Manual u control...
Page 72: ...72 2604080000 03 08 2020 Manual u control...