![Weco HeSU 5K3-LV HV Manual Download Page 58](http://html1.mh-extra.com/html/weco/hesu-5k3-lv-hv/hesu-5k3-lv-hv_manual_949484058.webp)
WeCo 5K3-LV-HV
HeSU 5K3-LV HV
Page 58 of 69
V_1.1_21-Nov-2020_LV-HV
Attention Azzurro CAN connection
To connect the WeCo Batteries with
ZCS Solar Inverter
(HYD 3 Ph 5-6-8-10-15-20kW) use only the CAN to Inverter
cable provided with the HV BOX KIT.
When is possible, WeCo suggest to reduce the CAN cable length in order to minimize the disturbs generated by the
Electromagnetic devices nearby the inverter and the batteries.
The cable provided it is crimped with a an RJ45 plug type 568B on one side while on the inverter end WeCo Provides naked
terminals to facilitate the connection with the ZCA AZZURRO terminal
CAN INVERTER CONNECTION
Pin Definition.
PIN 7 CAN H
PIN 8 CAN L
ZCS AZZURRO COM TERMINAL