WeCo 5K3-LV-HV
HeSU 5K3-LV HV
Page 56 of 69
V_1.1_21-Nov-2020_LV-HV
Step 4:
Link all modules and the HV box with a 6mm earthing cables ( In/Out) by using the GND connections point
Make sure that the ground connection is not shared with others potentials disturbing devices and that the ground rod is not used for
Neutral Line dispersion or Harmonics mitigation circuit