WECO 5K3-XP-EMEA
44
2.7.2 Shutdown of Parallel Batteries
Press and hold the Master Run Button for 5-seconds. The GREEN RUN light should go off immediately. The
GREEN RUN lights on the sub batteries will not be extinguished immediately.
The RED FAULT lights on the sub batteries
’
FRONT LED bars will start flashing after ten seconds and the GREEN
RUN lights will remain on.
After one minute the RED Fault lights on the FRONT LED bars and the GREEN RUN Button lights on all sub
batteries will go off.
Turn OFF the POWER SWITCH of each battery.
The parallel battery system has shutdown properly.
The RUN button might flash for several minutes, this process I normal when there is an upgrade ongoing or when there is a
new FW detected.
Even if the contactor is OPEN , ( OPEN CIRCUIT) the BMS can still operate in back ground, please let the process to
complete and wait for the RUN BUTTON to stop flashing waiting for the automatic shut down.
A forced shut down is possible by putting the main switch in (0) position, this might cause the interruption of FW
upgrade pushed from the APP or from the Local software XP MANAGER
NOTICE
:
When a Master battery is offline in a fault state, or has been manually shutdown, the entire cluster will go offline
until the Master comes back online.
To restart the Cluster, it is mandatory to repeat the Cluster Start Up procedure. First make sure to shut down all
batteries by setting the power switch to the off (0) position, then set all power switches to the ON (1) position and
press the master RUN BUTTON to enable the startup process again.
NOTICE
:
In a parallel battery system, we strongly advise not to switch off individual sub batteries when the system
is running either in Charge or Discharge Mode as this process might affect the communication between
modules and inverter.
Switching off an individual sub battery in a parallel system is possible in an adverse situation, but only as a last resort and
prior switching off the solar inverter