WECO 5K3-XP-EMEA
21
Step 2A:
In case of multiple module installation, make sure to respect the distance between the modules and the ceiling.
Example of a Floor or Wall Mounted battery cluster connected with power cables and data cables.
Note: In a single cluster configuration, there is no need to set the DIP switch on the master battery.
All DIP switches should be set to OFF with the only exception of the last module that needs to the Terminator
enabled, DIP 6 ON *( 120 Ohm R)
25 cm
25 cm
25 cm
25 cm
25 cm
Min 30 cm
Last Module Must Have DIP 6 ENABLED