0  10  20  30  40  50  60  70  80  90 

Zone Pressure psi

 0  1

1

4

"–1

1

2

    

100 110 

Do not reduce the size of the drain line from the air gap fit­

ting. The drain line must remain at full line size. 

E. After the initial installation of the assembly, a discharge from 

the relief valve may occur due to dirt and pipe compounds.  

This may be caused by inadequate initial flushing of the pipe­

lines. If flushing the valve does not clear the unit, remove the 

first check valve and clean thoroughly, using the procedures 

in “Servicing the First and Second Check Valves.” 

NOTICE

 

Periodic relief valve discharge may occur on dead end 

service applications, such as boiler feed lines or cooling 

tower makeup lines. This may be due to fluctuating supply 

pressure during a static or no flow condition. To avoid this 

discharge, install a spring-loaded, rubber seated check valve 

ahead of the backflow assembly. 

F.  Avoid placing the assembly in a pit or at a depth below 

the ground level, unless absolutely necessary. If an installa­

tion requires below ground level installation, a modified pit 

installation is recommended, as well as the approval of local 

codes. In such cases, provision should be made to always 

vent the drain line above the flood level. In the case of a pit 

drain, ensure an adequate air gap exists between the bottom 

of the drain line and the bottom of the pit. 

G. Periodically inspect the assembly to check for any discharge 

from the relief valve. This discharge is a visual indication that 

the valve needs cleaning or repair. Also test the valve peri­

odically in compliance with local codes to ensure its proper 

operation. 

The relief vent discharges water during no-flow periods in the 

following instances: 
• The first check valve is fouled.
• The inlet pressure to the check valve drops sufficiently due

to upstream pressure fluctuations. This affects the required

operating differential between the inlet pressure and the

reduced pressure zone.

• The second check is fouled during emergency backflow or

resulting from a water hammer condition.

For more information download Troubleshooting Guide S-TSG. 

NOTICE

 

When installing the assembly on fire prevention systems, special 

considerations are required. 
Fire Protection System Installations: The National Fire Protection 

Agency (NFPA) Guidelines require a confirming flow test to be 

conducted by a certified tester whenever a “main line” valve is 

installed, such as a shutoff valve or a backflow preventer. 

1

2

" – 1" 

45 
40 
35 
30 
25 
20 
15

Flow Rate gpm

10 


0  10  20  30  40  50  60  70  80  90  100 110 

Zone Pressure psi 

1

2

3

4

X 1" 

Flow Rate gpm 

50 

1

1

4

" – 2" 

350 
300 
250 

2" 

200 
150 
100 

TYPICAL FLOW RATES AS SIZED BY FLOOR DRAIN MANUFACTURERS 

2" 55 gpm 

5" 350 gpm 

3" 112 gpm 

6" 450 gpm 

4" 170 gpm 

8" 760 gpm 

Summary of Contents for LF919

Page 1: ...New Zealand line strainers should be installed between the upstream shutoff valve and the inlet of the backflow preventer If installed on a fire sprinkler system all mechanical checks such as alarm ch...

Page 2: ...of a single valve without shutting down the complete line The number of units installed in parallel should be determined by the engineer s judgment based on the operating conditions of a specific appl...

Page 3: ...an adequate air gap exists between the bottom of the drain line and the bottom of the pit G Periodically inspect the assembly to check for any discharge from the relief valve This discharge is a visua...

Page 4: ...hould point down toward the relief valve stem 3 Using a wrench reassemble the diaphragm assembly by turning the hex bolt clockwise to tighten Replacing the Relief Valve Disc and Seat 1 Using a Phillip...

Page 5: ...t it seats properly on the disc holder WARNING The first check valve has a heavyweight spring The second check valve has a lighter weight spring When reassembling the check valves install the correct...

Page 6: ...n the warranty period the Company will at its option replace or recondition the product without charge THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WI...

Page 7: ...tre le robinet d arr t en amont et l entr e du dispositif antirefoulement S il est install sur un syst mes de gicleurs d incendie toutes les v rifications m caniques par ex les alarmes et les disposit...

Page 8: ...e sans arr ter la conduite compl te Le nombre d unit s install es en parall le doit tre d termin par l expertise de l ing nieur en fonction des conditions de fonctionnement d une application sp cifiqu...

Page 9: ...eau d inondation Dans le cas d un drain de fosse assurez vous qu il y a un passage d air ad quat entre le bas de la conduite de vidange et le bas de la fosse G Inspectez r guli rement l ensemble pour...

Page 10: ...arge pression et le joint torique du si ge Remplacement du diaphragme 1 l aide d une cl desserrez l ensemble du diaphragme en tournant le boulon hexagonal dans le sens antihoraire 2 Retirez le diaphra...

Page 11: ...gag correctement avec le module du si ge 8 R ins rez l ensemble porte disque dans le module du si ge 9 Replacez le ressort en vous assurant qu il est bien en place sur le porte disque AVERTISSEMENT Le...

Page 12: ...exempt de vice de mat riau et de fabrication dans des conditions normales d utilisation pour une p riode d un an compter de la date d exp dition d origine Si une telle d faillance devait se produire...

Page 13: ...de l nea entre la v lvula de cierre de aguas arriba y la entrada del dispositivo de prevenci n de reflujo Si se instala en un sistema de rociadores contra incendios todas las verificaciones mec nicas...

Page 14: ...eta El n mero de unidades instaladas en paralelo debe determinarse seg n el criterio del ingeniero en funci n de las condiciones de funcionamiento de una aplicaci n espec fica AVISO La capacidad total...

Page 15: ...ar si hay alguna descarga de la v lvula de alivio Esta descarga es una indicaci n visual de que la v lvula necesita limpieza o reparaci n Pruebe tambi n la v lvula peri dicamente de acuerdo con los c...

Page 16: ...a v lvula de alivio a presi n y la junta t rica del asiento Sustituci n del diafragma 1 Con una llave afloje el conjunto del diafragma girando el perno hexagonal en sentido contrario a las manecillas...

Page 17: ...cubierta en el paso 12 la cubierta se acopla correctamente con el m dulo del asiento 8 Vuelva a insertar el conjunto del soporte del disco en el m dulo de asiento 9 Sustituya el muelle asegur ndose de...

Page 18: ...en condiciones de uso normal en el per odo de un a o a partir de la fecha de env o original En caso de que tales defectos se presenten dentro del per odo de garant a la Compa a a su criterio reemplaz...

Reviews: