background image

2

Installation Guidelines

Indoors

For indoor installation, make sure Series 919/LF919 is accessible 

to facilitate testing and servicing. Do not install the assembly 

in a concealed location. If the location is parallel and close to 

the wall, make sure the test cocks are accessible and the drain 

line can discharge water if required. An air gap and drain line 

are piped from the relief valve connection, allowing evidence of 

discharge to be visible and preventing the occurrence of water 

damage. (Refer to ES-AG/EL/TC at watts.com.)

Air Gap

Strainer

Meter

12" Minimum 

(refer to local codes)

Outdoor, Above Ground

For outdoor installations, install Series 919/LF919 where there 

are no freezing conditions and above ground whenever possible.
Install the assembly in an accessible location to facilitate testing 

and servicing. The installation must also allow for adequate 

drainage from the air gap and the discharge line if needed. 

 

WARNING

!

Do not allow the drain line to empty directly into a drainage 

ditch, sewer system, or sump. 
Do not install the assembly in any location where any part of the 

unit could become submerged in standing water. 

Now available, WattsBox Insulated Enclosures,

for more information, send for literature ES-WB.

Min. 12"

WattsBox Insulated Enclosure

For more information download ES-WB.

Parallel

For parallel installations, two or more small-sized assemblies 

can be installed (when approved) to serve a large supply pipe 

main. Use this type of installation in an application where 

increased capacity beyond that provided by a single valve is 

required. Additionally, this type of installation permits testing 

and/or servicing of a single valve without shutting down the 

complete line.
The number of units installed in parallel should be determined 

by the engineer’s judgment, based on the operating conditions 

of a specific application.

 

NOTICE

The total capacity of all the units installed in the application 

should equal or exceed that required by the system.

A.   Shutoff Valves: If you remove the shutoff valves from the 

assembly, reassemble the shutoff valve with the test cock 

mounted on the inlet side of the unit. 

B.   Check state and local codes to ensure the assembly is 

installed in compliance with the codes, such as proper height 

above the ground.

C.   Recommended: Install a strainer ahead of the assembly to 

protect the internal components from unnecessary fouling. 

  

CAUTION

!

 

Do not install the assembly with a strainer in rarely used 

water lines, such as a fire sprinkler system which is only 

deployed during emergencies. 

 

 Start Up: Close the downstream shutoff. Open the upstream 

slowly and fill the valve. When the valve is filled, open the 

downstream shutoff slowly, and fill the water supply system. 

This is necessary to avoid water hammer and/or shock 

damage. 

D.   Vent the air gap and drain line from the relief valve in accor-

dance with code requirements. Terminate discharge  approx-

imately 12" above the ground or through an air gap piped to 

a floor drain. 

 

WARNING

!

 

Do not allow the drain line to empty directly into a drainage 

ditch, sewer system, or sump. 

 

NOTICE

 

Relief Valve Discharge Rates. The air gap and drain line 

terminating above a floor drain can accommodate any mod-

erate discharge or nuisance spitting through the relief valve. 

However, to prevent water damage in the case of a cata-

strophic failure, design the floor drain size to accommodate 

the increased discharge. (See table on typical flow rates as 

sized by floor drain manufacturers, page 3.)  

 

NOTICE

 

Summary of Contents for LF919

Page 1: ...New Zealand line strainers should be installed between the upstream shutoff valve and the inlet of the backflow preventer If installed on a fire sprinkler system all mechanical checks such as alarm ch...

Page 2: ...of a single valve without shutting down the complete line The number of units installed in parallel should be determined by the engineer s judgment based on the operating conditions of a specific appl...

Page 3: ...an adequate air gap exists between the bottom of the drain line and the bottom of the pit G Periodically inspect the assembly to check for any discharge from the relief valve This discharge is a visua...

Page 4: ...hould point down toward the relief valve stem 3 Using a wrench reassemble the diaphragm assembly by turning the hex bolt clockwise to tighten Replacing the Relief Valve Disc and Seat 1 Using a Phillip...

Page 5: ...t it seats properly on the disc holder WARNING The first check valve has a heavyweight spring The second check valve has a lighter weight spring When reassembling the check valves install the correct...

Page 6: ...n the warranty period the Company will at its option replace or recondition the product without charge THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WI...

Page 7: ...tre le robinet d arr t en amont et l entr e du dispositif antirefoulement S il est install sur un syst mes de gicleurs d incendie toutes les v rifications m caniques par ex les alarmes et les disposit...

Page 8: ...e sans arr ter la conduite compl te Le nombre d unit s install es en parall le doit tre d termin par l expertise de l ing nieur en fonction des conditions de fonctionnement d une application sp cifiqu...

Page 9: ...eau d inondation Dans le cas d un drain de fosse assurez vous qu il y a un passage d air ad quat entre le bas de la conduite de vidange et le bas de la fosse G Inspectez r guli rement l ensemble pour...

Page 10: ...arge pression et le joint torique du si ge Remplacement du diaphragme 1 l aide d une cl desserrez l ensemble du diaphragme en tournant le boulon hexagonal dans le sens antihoraire 2 Retirez le diaphra...

Page 11: ...gag correctement avec le module du si ge 8 R ins rez l ensemble porte disque dans le module du si ge 9 Replacez le ressort en vous assurant qu il est bien en place sur le porte disque AVERTISSEMENT Le...

Page 12: ...exempt de vice de mat riau et de fabrication dans des conditions normales d utilisation pour une p riode d un an compter de la date d exp dition d origine Si une telle d faillance devait se produire...

Page 13: ...de l nea entre la v lvula de cierre de aguas arriba y la entrada del dispositivo de prevenci n de reflujo Si se instala en un sistema de rociadores contra incendios todas las verificaciones mec nicas...

Page 14: ...eta El n mero de unidades instaladas en paralelo debe determinarse seg n el criterio del ingeniero en funci n de las condiciones de funcionamiento de una aplicaci n espec fica AVISO La capacidad total...

Page 15: ...ar si hay alguna descarga de la v lvula de alivio Esta descarga es una indicaci n visual de que la v lvula necesita limpieza o reparaci n Pruebe tambi n la v lvula peri dicamente de acuerdo con los c...

Page 16: ...a v lvula de alivio a presi n y la junta t rica del asiento Sustituci n del diafragma 1 Con una llave afloje el conjunto del diafragma girando el perno hexagonal en sentido contrario a las manecillas...

Page 17: ...cubierta en el paso 12 la cubierta se acopla correctamente con el m dulo del asiento 8 Vuelva a insertar el conjunto del soporte del disco en el m dulo de asiento 9 Sustituya el muelle asegur ndose de...

Page 18: ...en condiciones de uso normal en el per odo de un a o a partir de la fecha de env o original En caso de que tales defectos se presenten dentro del per odo de garant a la Compa a a su criterio reemplaz...

Reviews: