Explanation of Function
Seite 88 / 180
(2) Instantaneous power failure during stop alarm output during under-voltage
Select yes/no of alarm output when instantaneous power failure or under-voltage occurs with b004.
Alarm outputs while control power of inverter remains.
(example5) b004 : 00
(example6) b004 : 01
(3) It is possible to use an output by assigning the signal (IP: 09) during instantaneous stop, by setting (RNT:
11) during under-voltage to an intelligent output terminal 11-15(C021-C025) or alarm relay output terminal
(C026).
Open phase protection function selection
This is the function to warn when the inverter input supply opens.
Functio
n code
Data Description
00 Invalid
Don’t trip when the input supply opens..
b006
01 Valid
Trip when the input supply opens..
(example3) Motor frequency(revolution time)
t0 t2
Free-run
Power supply
Inverter output
Motor
0
b007
F-equaling start
(example4) Motor frequency (revolution time)
t0
t2
Free-run
Power supply
Inverter output
Motor
0
b007
0Hz start
Power supply
AL
IP
Power supply
AL
IP
b006:Open phase selection
Relation code