Explanation of Function
Seite 100 / 180
11
speed ON OFF ON ON
12 speed
ON
ON
OFF OFF
13 speed
ON
ON
OFF
ON
14
speed ON ON ON
OFF
15
speed ON ON ON ON
(2) Bit operation
It is possible to set multi-speed 0 to 7 by assigning 32 to 38 (SF1-SF7) to the intelligent input terminals.
Set frequency SF1-SF7 to A021-A027.
Multi-sp
eed
SF7 SF6 SF5 SF4 SF3 SF2 SF1
0
speed
OFF OFF OFF OFF OFF OFF OFF
1
speed
- - - - - -
ON
2
speed
- - - - -
ON
OFF
3
speed
- - - -
ON
OFF
OFF
4
speed
- - -
ON
OFF
OFF
OFF
5
speed -
- ON OFF OFF OFF OFF
6
speed - ON OFF OFF OFF OFF OFF
7
speed ON OFF OFF OFF OFF OFF OFF
When each terminal turns ON simultaneously, the lower
number has priority.
In order for the inverter to operate
both
the frequency and the
RUN operation (FW,RV) must be applied.
1 speed
SF1
SF2
SF3
SF4
SF5
FW
0 speed
1 speed
2 speed
3 speed
4 speed 5 speed
Frequency command from
operator or analog external
input terminal