(1) Explanation of main circuit terminals
Symbol
Terminal Name
Explanation of contents
R, S, T
(L1,L2,L3)
Main power
Connect alternating power supply. When using regenerative converter and RG series,
don’t connect.
U, V, W
(T1,T2,T3)
Inverter output
Connect three-phase motor.
PD, P
(+1,+)
D.C.reactor
Remove the short bar between PD and P, connect optional Power factor reactor (DCL-XX).
P, RB
(+,RB)
External braking
resistor
Connect optional External braking resistor.
P, N
(+,-)
External braking unit
Connect optional Braking unit (BRD-XX).
(Installed on 11kW and 15kW)
G
Inverter earth
terminals
It is earth terminals of inverter case.
(2) Explanation of control circuit terminal
Symbol
Terminal Name
Explanation of contents
L
Analogue power common
It is common terminal of frequency command signal (0, 02, 01) and analogue output, AM,
AMI. Don’t earth.
H Frequency
power
It is the DC+10V power for terminals.
Allowable load current
20mA
O
Frequency command
power terminal (voltage)
When inputting DC O - 10V, it is maximum frequency on 10V.
When maximum frequency is expected to be on being less
than 10V, set with A014.
Input Impedance 10k ohm
Allowable maximum
voltage 12V
O2
Frequency command
support (voltage)
When inputting DC O - +-10V, this signal is added to
frequency command of 0 or 0I terminal.
Input Impedance 10k ohm
Allowable maximum load
current 20mA
OI
Frequency command
Terminal (current)
When inputting DC4 - 20mA, 20mA is maximum frequency.
When only At terminal is ON, this input signal is effective.
Input Impedance 100 ohm
Allowable maximum
current 24mA
AM Digital
monitor
(voltage)
Allowable maximum
current 2mA
AMI
Analogue monitor
(current)
Output one selected from monitor item, output frequency,
output current, torque, output voltage, input electric power,
electric thermal rate.
Allowable output less than
Impedance 250 ohm
FM
Digital monitor
(voltage)
Output the output frequency with digital besides above
monitor.
Allowable maximum
current 1.2mA
Maximum frequency
3.6khz
P24 Interface
power
It is DC24V power for connection input signal. When
selecting source logic, it’s for connection input common.
Allowable maximum
output current 100mA
CM1
Interface power common
The common terminal is FW terminal, 1 - 8 terminal, TH terminal, FM terminal,
Don’t earth.
PLC
Intelligent input common
Change sink type and source type by short bar on control terminals.
P24-PLC : Sink type CM1-PLC : Source type
FW
Forward command
About FW signal, ON is Forward and OFF is stop command.
1
2
3
4
5
6
7
8
Input intelligent
Select 8 functions from 33 functions, and divide between 1
terminal and 8 terminals.
Allowable maximum
voltage 27V
Input impedance
4.7k ohm
11
12
13
14
15
output intelligent
Select 8 functions from 13 functions, and divide between 1
terminal and 5 terminals
Allowable maximum
voltage 27V
current 5mA
AL1
AL2
Alarm output terminal
Assign output function. Output is c contact.
AL0 Common
terminal
It is common terminal of alarm output terminal
Allowable maximum
AC250V,0.2A
Allowable minimum
AC100V,10mA
TH
Thermistor input terminal
When a Thermistor is connected to terminals TH and CM1,the
Inverter checks for over-temperature and will cause trip event
and turn off output to motor.
Allowable minimum
Thermistor Power
100mW