Explanation of Function
Seite 113 / 180
Setting item
Function code
Setting range
Contents
Control method selection
A044/A244
/A344
03
04
05
SLV (A344 is not)
0 Hz domain SLV (A344 is not)
V2 (A344)
Intelligent input selection
C001 - C008
43
PPI : P/PI switching
Speed response
H005/H205
0.01 - 99.99
Unit : no demension
PI proportion gain
H050/H250
1.0 -
999.9/1000
Unit : %
PI integration gian
H051/H251
1.0 -
999.9/1000
Unit : %
P proportion gain
H052/H252
1.0 -
999.9/1000
Unit : %
PI proportion gain for
switching
H070 1.0
-
999.9/1000
Unit : %
PI integration gain for
switching
H071 1.0
-
999.9/1000
Unit : %
P proportion gain for
switvhing
H072 1.0
-
999.9/1000
Unit : %