The modules can also be mounted in different locations and the backplane connected via wires in a
Split
Rail
configuration as shown in the figure. Notice in the split rail system diagram that a single power
supply is used across both DIN rails. One notable consideration when designing the hardware layout
would be the available power supplied and the loading effect of all of the modules used.
Watlow provides three options for power supplies listed below:
•
90-264VAC to 24VDC @ 31 watts (Part #: 0847- 0299-0000)
•
90-264VAC to 24VDC @ 60 watts (Part #: 0847- 0300-0000)
•
90-264VAC to 24VDC @ 91 watts (Part #: 0847- 0301-0000)
With regards to the modular loading affect, maximum power for each is listed below:
•
RMCxxxxxxxxxxxx @ 7 watts / 14VA
•
RMEx-xxxx-xxxx @ 7 watts / 14VA
•
RMHx-xxxx-xxxx @ 7 watts / 14VA
•
RMLx-xxxx-xxxx @ 7 watts / 14VA
•
RMSx-xxxx-xxxx @ 7 watts / 14VA