Version 1.0
PN: 2042-8198
Page 70 of 75
DN: 10-32813
Full file name / path where the HTTP server configuration file lives. Elements in this file are used for
displaying system parameters on custom web pages. This record is not a member of the default file. If
you wish to use this feature, you must add this record to the setup file. See
MACA(1-3)
Key
Value
MACA1
C8:5B:76:F2:6F:06
MACA2
C8:5B:76:F2:6F:07
MACA3
C8:5B:76:F2:6F:08
MAC address(es) for Ethernet MAC filtering. Each MAC address is a string consisting of six hexadecimal
octets separated by a colon. The MAC will only allow requests from the MAC addresses specified in this
file. These records are not members of the default file, and therefore, the feature is disabled. If you
wish to use this feature, you must add one or more records to the setup file. See
SntpAddress
Key
Value
SntpAddress
216.239.35.4
Ethernet IPV4 address of a SNTP server as a string. This record is not a member of the default file, and
therefore, the feature is disabled. If you wish to use this feature, you must add this record to the setup
file. See
SnifferPort
Key
Value
SnifferPort
2
This key defines the port that will mirror all packets received and transmitted on port 3 (internal switch
connection to RMA PLUS). Acceptable values are 1 and 2 as labeled on the front of the RMA PLUS. Zero
is the default value which disables this feature. This record is not a member of the default file, and
therefore, the feature is disabled. If you wish to use this feature, you must add this record to the setup
file. See
Discover
Key
Value
Discover
1
This key enables or disables the Watbus Over Ethernet (WOE) discovery feature. It is a Boolean option,
enabled by default. Setting this value to 0 will prevent software tools from discovering the device. This
record is not a member of the default file. If you wish to use this feature, you must add this record to
the setup file. Refer to the following table:
Value
Action
0
(FALSE)
Discovery disabled
1
(TRUE)
Discovery enabled
DataLog
Key
Value
DataLog
nor:\Gateway\DataLog.csv
This key only applies if the model number is RMAP-XX
D
X-XXXX.
Full file name / path where the data log configuration file lives. Elements in this file will be written to a
log file at a pre-defined interval. See
Summary of Contents for RMA PLUS RMAP-AA Series
Page 1: ...Version 1 0 PN 2042 8198 Page 1 of 75 DN 10 32813 RMA PLUS User Manual...
Page 8: ...Version 1 0 PN 2042 8198 Page 8 of 75 DN 10 32813...
Page 11: ...Version 1 0 PN 2042 8198 Page 11 of 75 DN 10 32813 Figure 3 Ground Wire Location...
Page 26: ...Version 1 0 PN 2042 8198 Page 26 of 75 DN 10 32813 Figure 22 RMA PLUS via USBD MICRO SD root...
Page 27: ...Version 1 0 PN 2042 8198 Page 27 of 75 DN 10 32813 Figure 23 RMA PLUS via USBD NOR FLASH root...
Page 42: ...Version 1 0 PN 2042 8198 Page 42 of 75 DN 10 32813 Figure 37 Default web page Index html...
Page 75: ...Version 1 0 PN 2042 8198 Page 75 of 75 DN 10 32813...