Version 1.0
PN: 2042-8198
Page 47 of 75
DN: 10-32813
Notes
•
Read-only files cannot be written via TFTP
•
Binary image transfer mode [-i] is recommended to prevent data loss in some strings
Command Format using Windows® 7 native TFTP client:
TFTP [-i] host [GET | PUT] source [destination]
Sample Read
Read the Modbus TCP configuration file (ModbusTcp.csv) from the NOR FLASH drive and place it in a
folder in the temporary directory.
TFTP -i rma-1894854 GET nor:\Gateway\ModbusTcp.csv %TEMP%\TFTP\ModbusTcp.csv
Sample Write:
Write the Modbus TCP configuration file (ModbusTcp.csv) from a folder in the temporary directory to
the NOR FLASH drive.
TFTP -i rma-1894854 PUT %TEMP%\TFTP\ModbusTcp.csv nor:\Gateway\ModbusTcp.csv
SNTP Client
The RMA PLUS implements a Simple Network Time Protocol (SNTP) client. If the configuration key
is present, the RMA PLUS will attempt to synchronize its time with the configured SNTP
server once per day. If the connection fails, the RMA PLUS will try again at a faster interval until the
connection is successful.
Wireshark
Wireshark is an Ethernet network analyzer. If you are trying to diagnose an Ethernet issue, Wireshark is
an invaluable tool. The factory may ask for a network capture to help diagnose problems.
If the problem is between PC software and the RMA PLUS, you can install Wireshark on the PC with no
additional configuration. If the problem is between a device without Wireshark and the RMA PLUS, you
can activate the port mirroring feature of the embedded switch to obtain a network capture.
Watbus
Watbus is a RS-485 token-passing network that may contain both masters and slaves. It is a proprietary
protocol that all products implement. There are two varieties
–
high-speed and low-speed. The RMA
PLUS is a master on both channels.
The logical address is independently software selectable for each bus. Use Standard Bus Instance 1 to
change the logical address for low-speed Watbus. Use Standard Bus Instance 2 to change the logical
address for high-speed Watbus.
for member documentation.
Address Segmentation
The legacy bus (low-speed Watbus) is segmented and thus requires an additional configuration
parameter to address data points. Therefore, when you purchase an EZ-ZONE RUI and EZ-ZONE PM, and
Summary of Contents for RMA PLUS RMAP-AA Series
Page 1: ...Version 1 0 PN 2042 8198 Page 1 of 75 DN 10 32813 RMA PLUS User Manual...
Page 8: ...Version 1 0 PN 2042 8198 Page 8 of 75 DN 10 32813...
Page 11: ...Version 1 0 PN 2042 8198 Page 11 of 75 DN 10 32813 Figure 3 Ground Wire Location...
Page 26: ...Version 1 0 PN 2042 8198 Page 26 of 75 DN 10 32813 Figure 22 RMA PLUS via USBD MICRO SD root...
Page 27: ...Version 1 0 PN 2042 8198 Page 27 of 75 DN 10 32813 Figure 23 RMA PLUS via USBD NOR FLASH root...
Page 42: ...Version 1 0 PN 2042 8198 Page 42 of 75 DN 10 32813 Figure 37 Default web page Index html...
Page 75: ...Version 1 0 PN 2042 8198 Page 75 of 75 DN 10 32813...