In this example, additional records may be added starting at registers 2 and 1002 because both
elements are 32-bit values.
•
A value of 0 will be returned for registers that are not explicitly defined in the table.
•
An exception will be returned if a request exceeds the limits of the table i.e. Register > 1001 in this
example.
•
Writing will not return an exception unless the above condition is violated.
Register
Bus
Segment
Zone
Class
Instance
Member
Refresh Count
0
1
0
0
1
1
1
0
DEV 1 Hardware ID
1000
1
0
0
36
1
19
0
RTC 1 Timestamp
Figure 33 - ModbusTcp.csv default configuration
Perform test read / write operations on the data. A sample Modbus® TCP test program is included on
the MICRO SD drive for testing purposes (sd:\Software\Modbus TCP). In the following example, the
RMA PLUS’s
Hardware ID (32-bit Integer) is returned for registers 0, 1. Registers 2 and 3 were not
specified so they return 0s.
Figure 34 - Example: Modbus TCP client
Attempting to read beyond the ends of the defined table will return an exception.
Summary of Contents for RMA PLUS RMAP-AA Series
Page 1: ...Version 1 0 PN 2042 8198 Page 1 of 75 DN 10 32813 RMA PLUS User Manual...
Page 8: ...Version 1 0 PN 2042 8198 Page 8 of 75 DN 10 32813...
Page 11: ...Version 1 0 PN 2042 8198 Page 11 of 75 DN 10 32813 Figure 3 Ground Wire Location...
Page 26: ...Version 1 0 PN 2042 8198 Page 26 of 75 DN 10 32813 Figure 22 RMA PLUS via USBD MICRO SD root...
Page 27: ...Version 1 0 PN 2042 8198 Page 27 of 75 DN 10 32813 Figure 23 RMA PLUS via USBD NOR FLASH root...
Page 42: ...Version 1 0 PN 2042 8198 Page 42 of 75 DN 10 32813 Figure 37 Default web page Index html...
Page 75: ...Version 1 0 PN 2042 8198 Page 75 of 75 DN 10 32813...