Watlow EZ-ZONE
®
PM PID Controller
•
65
•
Chapter 7 Profiling Page
Profiling Page
Dis-
play
Parameter name
Description
Range
Default
Parameter
Appears in
Menu When
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Data
Type
&
Read/
Write
[~SEC]
[ SEC]
Step Type Parameters
Seconds
Select the seconds (plus
Hours and Minutes) for a
timed step.
0 to 59
0
Step Type is
set to Time or
Soak.
Instance 1
Map 1
Map 2
2578
4508
Offset to next
instance (
Map
1 50,
Map 2
equals
+100)
0x79 (121)
1 to 40
5
uint
RWE
W;P1]
[W.P1]
Step Type Parameters
Wait For Process Value
Select which analog input
Wait For Process will use.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
Step Type is
set to Wait For
Process.
Instance 1
Map 1
Map 2
2590
4520
Offset to next
instance (
Map
1 50,
Map 2
equals
+100)
0x79 (121)
1 to 40
0xB (11)
float
RWE
WE;1]
[WE.1]
Step Type Parameters
Wait Event (5-6)
Select the event state that
must be satisfied during
this step. Digital input 5
provides the state of Event
1, and digital input 6 pro-
vides the state of Event 2.
[`oFF]
Off (62)
[``on]
On (63)
[nonE]
None (61)
Off
Step Type is
set to Wait
Event or Wait
for Both.
Instance 1
Map 1
Map 2
2586
4516
Offset to next
instance (
Map
1 50,
Map 2
equals
+100)
0x79 (121)
1 to 40
9
uint
RWE
[WE;2]
[WE.2]
Step Type Parameters
Wait Event (5-6)
Select the event state that
must be satisfied during
this step. Digital input 5
provides the state of Event
1, and digital input 6 pro-
vides the state of Event 2.
[`oFF]
Off (62)
[``on]
On (63)
[nonE]
None (61)
Off
Step Type is
set to Wait
Event or Wait
for Both.
Instance 1
Map 1
Map 2
2588
4518
Offset to next
instance (
Map
1 50,
Map 2
equals
+100)
0x79 (121)
1 to 40
0xA (10)
uint
RWE
[dow]
[dow]
Step Type Parameters
Day of Week
[``ed]
Every Day (1567)
[`wd]
Week days (1566)
[`sun]
Sunday (1565)
[mon]
Monday (1559)
[`tue]
Tuesday (1560)
[wed]
Wednesday (1561)
[thUr]
Thursday (1562)
[`fri]
Friday (1563)
[`sat]
Saturday (1564)
Sunday
If real time
clock is present
and StepType
is set to Wait
for Time.
Instance 1
Map 1
Map 2
- - - -
4580
Offset to next
instance
Map 2
100)
0x79 (121)
1 to 40
0x29 (41)
uint
RWE
[~~JS]
[ JS]
Step Type Parameters
Jump Step
Select a step to jump to.
1 to 40
0
Step Type is
set to Jump
Loop.
Instance 1
Map 1
Map 2
2592
4522
Offset to next
instance (
Map
1 50,
Map 2
equals
+100)
0x79 (121)
1 to 40
0xC (12)
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.
R: Read
W: Write
E:
EEPROM