Watlow EZ-ZONE
®
PM PID Controller
•
59
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range
Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[``Fn]
[ Fn]
Function Key (1 to 2)
Digital Input Func-
tion
Program the EZ Key
to trigger an action.
Functions respond to a
level state change or
an edge level change.
[none]
None (61)
[P;StS]
Profile Start/Stop,
level triggered (208)
[ProF]
Profile Start Num-
ber, edge triggered (196)
[P;hoL]
Profile Hold/
Resume, level triggered
(207)
[P;diS]
Profile Disable,
level triggered (206)
[`t;da]
TRU-TUNE+
®
Dis-
able, level triggered (219)
[`oFF]
Control Outputs
Off, level triggered (90)
[MAn]
Manual/Auto
Mode, level triggered (54)
[tUnE]
Tune, edge trig-
gered (98)
[idLE]
Idle Set Point En-
able, level triggered (107)
[`F;AL]
Force Alarm, level
triggered (218)
[`AoF]
Alarm Outputs &
Control Loop Off, level
triggered (220)
[`SiL]
Silence Alarms,
edge triggered (108)
[ALM]
Alarm Reset, edge
triggered (6)
[P;LoC]
Lock Keypad, level
triggered (217)
[usr;r]
Restore User Set-
tings, edge triggered
(227)
None
Always
Instance 1
Map 1 Map 2
1324
1564
Instance 2
Map 1 Map 2
1344
1584
0x6E (110)
1 to 2
3
138
uint
RWES
[``Fi]
[ Fi]
Function Key (1 to 2)
Instance
Select which instance
the EZ Key will affect.
If only one instance is
available, any selec-
tion will affect it.
0 to 4
0
Always
Instance 1
Map 1 Map 2
1326
1566
Instance 2
Map 1 Map 2
1346
1586
0x96 (110)
1 to 2
4
139
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which scale to
use for temperature.
[```F]
°F (30)
[```C]
°C (15)
°F
Always
110
[AC;LF]
[AC.LF]
Global
AC Line Frequency
Set the frequency to
the applied ac line
power source.
[``50]
50 Hz (3)
[``60]
60 Hz (4)
60 Hz
Always
Instance 1
Map 1 Map 2
886
1006
0x6A (106)
1
4
89
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
*
Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set