Watlow EZ-ZONE
®
PM PID Controller
•
61
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range
Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[Ad;M]
[Ad.M]
Communications (1)
Address Modbus
Set the network ad-
dress of this control-
ler. Each device on the
network must have a
unique address.
1 to 247
1
Protocol
is set to
Modbus.
Instance 1
Map 1 Map 2
2482
2962
0x96 (150)
1
2
- - - -
uint
RWE
[bAUd]
[bAUd]
Communications (1)
Baud Rate Modbus
Set the speed of this
controller's communi-
cations to match the
speed of the serial
network.
9,600 (188)
19,200 (189)
38,400 (190)
9,600
Protocol
is set to
Modbus.
Instance 1
Map 1 Map 2
2484
2964
0x96 (150)
1
3
- - - -
uint
RWE
[`PAr]
[ PAr]
Communications
Parity Modbus
(1)
Set the parity of this
controller to match
the parity of the serial
network.
[none]
None (61)
[EuEn]
Even (191)
[`odd]
Odd (192)
None
Protocol
is set to
Modbus.
Instance 1
Map 1 Map 2
2486
2966
0x96 (150)
1
4
- - - -
uint
RWE
[M;hL]
[M.hL]
Communications (1)
Modbus Word Order
Select the word or-
der of the two 16-bit
words in the floating-
point values.
[Lohi]
Low-High (1331)
[hiLo]
High-Low (1330)
Low-High Protocol
is set to
Modbus.
Instance 1
Map 1 Map 2
2488
2968
0x96 (150)
1
5
- - - -
uint
RWE
[Map]
[ Map]
Communications (1)
Data Map
If set to 1 the control
will use PM legacy
mapping. If set to 2
the control will use
new mapping to ac-
commodate new func-
tions.
1 to 2
1
Always
- - - -
[`nU;S]
[ nV.S]
Communications (1)
Non-volatile Save
If set to Yes all values
written to the control
will be saved in EE-
PROM.
[`yes]
Yes (106)
[``no]
No (59)
Yes
Always
Instance 1
Map 1 Map 2
2494
2974
0x96 (150)
1
8
198
uint
RWE
[rtC]
*
[`SEt]
Real Time Clock Menu
[hoUr]
[hoUr]
Real Time Clock
Hours
0 to 23
0
Always if
4th digit
in part
number is
a "B" or
"E".
Instance 1
Map 1 Map 2
- - - -
4004
88 (136)
1
3
- - - -
uint
RW
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
*
Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set