Watlow EZ-ZONE
®
PM PID Controller
•
50
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range
Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[``Fn]
[ Fn]
Digital Input (5 to 6)
Action Function
Select the function
that will be triggered
by a true state for
Event Level 1 (DI5)
and Event Level 2
(DI6).
[none]
None (61)
[lmr]
Limit Reset (82)
[P;StS]
Profile Start/Stop
(208)
[ProF]
Start Profile (196)
[P;hoL]
Profile Hold/Re-
sume (207)
[P;diS]
Profile Disable
(206)
[`t;dA]
TRU-TUNE+™
Disable (219)
[`off]
Off (62)
[MAn]
Manual (54)
[tUnE]
Tune (98)
[idLE]
Idle Set Point
(107)
[`F;AL]
Force Alarm to
Occur (218)
[`AoF]
Control Loops Off
and Alarms to Non-alarm
State (220)
[`SiL]
Silence Alarms
(108)
[ALM]
Alarm (6)
[p;loc]
Keyboard lockout
(217)
[USr;r]
User Settings Re-
store (227)
Direction is
set to Out-
put.
Instance 1
Map 1 Map 2
1324
1564
Offset to next
instance (
Map
1 & Map 2
)
20
0x6E (110)
1 to 2
3
138
uint
RWES
[``Fi]
[ Fi]
Digital Input (5 to 6)
Function Instance
Select which instance
of the Event Function
that will be triggered
by a true state.
-Event/Instance 1 goes
with DI5
-Event/Instance 2 goes
with DI6
-Event/Instance 3 goes
with
EZ-Key
0 to 4
0
Direction is
set to Out-
put.
Instance 1
Map 1 Map 2
1326
1562
Offset to next
instance (
Map
1 & Map 2
)
20
0x6E (110)
5 to 7
4
139
uint
RWES
[LooP]
[`Set]
Control Loop Menu
[`h;Ag]
[ h.Ag]
Control Loop (1)
Heat Algorithm
Set the heat control
method.
[`oFF]
Off (62)
[`Pid]
PID (71)
[on;of]
On-Off (64)
PID
Always
Instance 1
Map 1 Map 2
1884
2364
0x97 (151)
1
3
72
uint
RWES
[`C;Ag]
[ C.Ag]
Control Loop (1)
Cool Algorithm
Set the cool control
method.
[`oFF]
Off (62)
[`Pid]
PID (71)
[on;of]
On-Off (64)
Off
Always
Instance 1
Map 1 Map 2
1886
2366
0x97 (151)
1
4
73
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
*
Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set