Watlow EZ-ZONE
®
PM PID Controller
•
57
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range
Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`A;hy]
[ A.hy]
Alarm (1 to 4)
Hysteresis
Set the hysteresis for
an alarm. This deter-
mines how far into
the safe region the
process value needs to
move before the alarm
can be cleared.
0.001 to 9,999.000°F or
units
0.001 to 5,555.000°C
1.0°F or
units
1.0°C
Type is not
set to Off.
Instance 1
Map 1 Map 2
1484
1884
Offset to next
instance (
Map
1 50,
for Map 2
60)
0x6D (109)
1 to 4
3
24
float
RWES
[`A;Lg]
[ A.Lg]
Alarm (1 to 4)
Logic
Select what the out-
put condition will
be during the alarm
state.
[`AL;C]
Close On Alarm
(17)
[`AL;o]
Open On Alarm
(66)
Close On
Alarm
Type is not
set to Off.
Instance 1
Map 1 Map 2
1488
1888
Offset to next
instance (
Map
1 50,
for Map 2
60)
0x6D (109)
1 to 4
5
25
uint
RWES
[`A;Sd]
[ A.Sd]
Alarm (1 to 4)
Sides
Select which side or
sides will trigger this
alarm.
[both]
Both (13)
[high]
High (37)
[LoW]
Low (53)
Both
Type is not
set to Off.
Instance 1
Map 1 Map 2
1486
1886
Offset to next
instance (
Map
1 50,
for Map 2
60)
0x6D (109)
1 to 4
4
26
uint
RWES
[`A;LA]
[ A.LA]
Alarm (1 to 4)
Latching
Turn alarm latching
on or off. A latched
alarm has to be
turned off by the user.
[nLAt]
Non-Latching (60)
[`LAt]
Latching (49)
Non-
Latching
Type is not
set to Off.
Instance 1
Map 1 Map 2
1492
1892
Offset to next
instance (
Map
1 50,
for Map 2
60)
0x6D (109)
1 to 4
7
27
uint
RWES
[`A;bL]
[ A.bL]
Alarm (1 to 4)
Blocking
Select when an alarm
will be blocked. After
startup and/or after
the set point changes,
the alarm will be
blocked until the pro-
cess value enters the
normal range.
[`oFF]
Off (62)
[`Str]
Startup (88)
[StPt]
Set Point (85)
[both]
Both (13)
Off
Type is not
set to Off.
Instance 1
Map 1 Map 2
1494
1894
Offset to next
instance (
Map
1 50,
for Map 2
60)
0x6D (109)
1 to 4
8
28
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
*
Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User