Trouble Shooting Chart—Continued
Symptom
Symptom
Possible Cause
Possible Cause
Solution
Solution
The foam system does not output
concentrate.
The power is not on.
Turn on the power.
The foam strainer is plugged.
Clean or replace the strainer.
The pressure relief valve is set too low.
Reset or replace the pressure relief valve.
The shutoff valve is closed.
Open the shutoff valve.
The inject/bypass valve is in the bypass position.
Set the valve to the inject position.
The foam concentrate is too viscous (above 2000 centipoise).
Use foam with lower viscosity (below 2000 centipoise) and calibrate the
system for the foam being used.
The foam pump and OIT have power
but do not inject concentrate when
enabled.
No water is flowing in any of the foam discharges.
Flow water through a foam capable discharge.
The flowmeter cable is malfunctioning.
Replace the flowmeter cable.
The paddle wheels on the flowmeter are obstructed or damaged.
Clear any obstructions or replace the flowmeter.
There is an unexpected flow
measurement.
An incorrect unit of measurement has been selected in the menu.
Use another measurement method or change the unit of measurement in
the menu.
The OIT is displaying nCon.
The concentrate supply tank is empty.
Add concentrate to the tank.
The concentrate tank level switch is malfunctioning.
Repair or replace the switch or cable.
The red LED on the manual OIT is
illuminated.
The concentrate supply tank is empty.
Add concentrate to the tank.
The concentrate tank level switch is malfunctioning.
Repair or replace the switch or cable.
The mix does not output from the
nozzle as expected.
The mix percentage is set too low.
Increase the mix percentage.
The foam system is not primed.
Prime the foam system.
There is low foam volume.
Increase the mix percentage.
The OIT does not illuminate.
No power to the OIT.
Check the power cable to the controller and the OIT cable.
The master power on the vehicle is not enabled.
Enable the master power.
The circuit breaker switch has tripped.
Reset the circuit breaker.
The green LED on the OIT does not
flash when you flow water though the
flowmeter tee or manifold.
The flowmeter cable is malfunctioning.
Replace the flowmeter cable.
The paddle wheel on the flowmeter is obstructed or damaged.
Clear any obstructions or replace the flowmeter.
The OIT is displaying horizontal bars.
There is a communication error between the OIT and the controller.
Verify that the pins on the cable are not bent, then replace the cable if they
are damaged. Contact Waterous to replace the control box.
The foam concentrate is entering the
water tank.
Concentrate was poured into the water tank.
Flush the water tank.
There is a leak between the water and foam tanks.
Repair or replace the tanks.
A check valve in the waterway is malfunctioning.
Clear any obstructions or replace the check valve.
The drain line for the foam manifold is not isolated.
Isolate the drain line for the foam manifold.
The green LED on the OIT does not
illuminate, but a value is displayed.
The foam system is not on.
Press the foam button.