36
Connecting Data and Supply Cables
WAGO-SPEEDWAY 767
767-9101 Power Divider, 24 VDC
Manual
Version 3.0.0
Pos: 23.16 /Serie 767 ( WAGO-SPEED WAY)/Anschluss D aten- und Versorgungskabel/I/O-M odule/Anschluss_M 12- Versorgungsleitung en 767-9101 @ 8\mod_1278313678666_21.docx @ 58951 @ 2 @ 1
5.4
Connecting M12 Supply Cable
The M12 supply cable with maximum 0.75 mm² cross section supplies 767 Series
components (individual and/or group supply)
Requirement:
The WAGO supply cables pre-assembled on both ends must be available (K1 and
K2 in the figure on the next page).
The following table outlines the assignment of the supply connections:
Table 12: Supply outputs: connection assignment
Connection
Contact
Description
OUT
OUT 1
24V U
LS
2
24V U
A
3
0V U
LS
4
0V U
A
5
Not assigned
Pos: 23.17 /Serie 767 ( WAGO-SPEED WAY)/Wichtige Erläuter ung en/Sicherheitshinweise/Achtung/Achtung: Höchste Strombel astbar keit M 12 @ 8\mod_1278308104531_21.docx @ 58907 @ @ 1
The highest current carrying capacity of the M12 supply contacts is 4A!
Supply lines U
LS
and U
A
of the M12 supply outputs shall each be charged with a
maximum of 4A. If the maximum current carrying capacity is exceeded, both the
connectors and components will be damaged. The module supply output is not
automatically monitored for overload.
Pos: 23.18 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1