WAGO-SPEEDWAY 767
Connecting Data and Supply Cables
33
767-9101 Power Divider, 24 VDC
Manual
Version 3.0.0
Pos: 23.1 /Serie 767 (WAGO-SPEED WAY)/Anschl uss D aten- und Versorgungskabel/I/O-Modul e/01_Anschl uss der Daten- und Versorgungskabel - Überschrift 1 @ 8\mod_1278310189976_21.docx @ 58919 @ 1 @ 1
5
Connecting Data and Supply Cables
Pos: 23.2 /Serie 767 (WAGO-SPEED WAY)/Anschl uss D aten- und Versorgungskabel/I/O-Modul e/02_Hinweise - Ü berschrift 2 @ 8\mod_1278310190960_21.docx @ 58923 @ 2 @ 1
5.1
Notes
Pos: 23.3 /Serie 767 (WAGO-SPEED WAY)/Wichtige Erläuterungen/Sicherheitshinweise/Gefahr/Gefahr: El ektrische Spannung @ 8\mod_1278307980373_21.docx @ 58901 @ @ 1
Electric voltage!
Operate the 767 Series components exclusively with 24 VDC PELV (Protective
Extra Low Voltage) or SELV (Safety Extra Low Voltage) voltage sources. Failure
to comply may result in electric shock.
Pos: 23.4 /Serie 767 (WAGO-SPEED WAY)/Wichtige Erläuterungen/Sicherheitshinweise/Achtung/Achtung: H öchste Strombelastbar keit M23 @ 8\mod_1278308039077_21.docx @ 58904 @ @ 1
The highest current carrying capacity of the M23 supply contacts is 24A!
The supply lines of the M23 supply input shall only be charged with a maximum
of 8A for U
LS
and 16A for U
A
. If the maximum current carrying capacity is
exceeded, both the connectors and components will be damaged. The module
supply input is not automatically monitored for overload.
Pos: 23.5 /Serie 767 (WAGO-SPEED WAY)/Wichtige Erläuterungen/Sicherheitshinweise/Achtung/Achtung: H öchste Strombelastbar keit M12 @ 8\mod_1278308104531_21.docx @ 58907 @ @ 1
The highest current carrying capacity of the M12 supply contacts is 4A!
Supply lines U
LS
and U
A
of the M12 supply outputs shall each be charged with a
maximum of 4A. If the maximum current carrying capacity is exceeded, both the
connectors and components will be damaged. The module supply output is not
automatically monitored for overload.
Pos: 23.6 /Serie 767 (WAGO-SPEED WAY)/Wichtige Erläuterungen/Sicherheitshinweise/Achtung/Achtung: Offene Anschlüsse @ 8\mod_1278308159953_21.docx @ 58910 @ @ 1
Exposed connections!
If connections have not been closed with protective caps, liquid or dirt can
penetrate the components of the 767 Series module and ruin it. Therefore, close
all unnecessary connections with protective caps, which must be ordered
separately, in order to maintain the IP67 degree of protection. (See "Accessories"
section of the fieldbus coupler/controller manual.)
Pos: 23.7 /Serie 767 (WAGO-SPEED WAY)/Anschl uss D aten- und Versorgungskabel/I/O-Modul e/Anschl uss_Hinweise allgemeiner T eil 1 @ 5\mod_1249286391531_21.docx @ 39858 @ @ 1
•
The connectors must be disconnected from the power supply when screws
are tightened.
•
Tighten the connectors by hand. To achieve the required torque (see below)
for the connector, use the torque wrench with the order number 206-701.
Using other mechanical aids can lead to stripping the threads, which will
require replacement of the module.
Pos: 23.8 /Serie 767 (WAGO-SPEED WAY)/Anschl uss D aten- und Versorgungskabel/I/O-Modul e/Anschl uss_Anzugsmomente 767- 9101 @ 7\mod_1267768998499_21.docx @ 51750 @ @ 1
Tightening torques for the connectors:
Supply outputs, M12: 1.0 Nm
Pos: 23.9 /Serie 767 (WAGO-SPEED WAY)/Anschl uss D aten- und Versorgungskabel/I/O-Modul e/Anschl uss_Hinweise Weiterleitung 767-9101 @ 8\mod_1278315196088_21.docx @ 58963 @ @ 1