Parameterizing
WAGO-SPEEDWAY 767
767-5201 TTL Incremental/SSI Encoder
Manual
Version 1.1.0
Pos: 30.22 /Serie 767 ( WAGO-SPEED WAY)/Parametrier en/I/O-Module/Parametrier ung 767-5201, -5202 Parameter der F eldversorgung @ 14\mod_1363274097021_21.docx @ 114524 @ 2 @ 1
7.7
Field Supply Parameters
Table 46: Parameters for the field supply
Parameter
Description:
Enable field supply
Switch on the field supply here.
Default setting: selected
Autorestart delay
In the event of a short circuit, the field supply is switched off for a
parameterizable amount of time.
Use this field to enter the time delay (in intervals of 100 ms), after
which the field supply is to be restarted..
If the short circuit condition persists, the process is repeated.
Default setting: 10
Supply voltage
Select the supply voltage here. You have the following options:
Field supply X1 and X2
24 V*
Field supply X3 and X4
5 V
24 V*
Diagnostic Simulation
The simulation can be used to simulate a short circuit.
Default setting: unselected
Short circuit/Overload
"Simulation diagnosis" unselected:
If a short circuit/open load occurs, the appropriate diagnosis is displayed
here.
If the "Simulation diagnosis" parameter has been selected, you can
simulate the associated error by selecting the appropriate parameter.
* Factory default setting