WAGO-SPEEDWAY 767
Parameterizing
63
767-5201 TTL Incremental/SSI Encoder
Manual
Version 1.1.0
Table 38: Overview of adjustable parameters for the counter
Parameter
Description:
Lower limit
The lower limit value can be defined here. If the counter reading lies
outside of the defined range, a limiting value signal is generated – this is
available as a status bit in the process image.
Enter a value (-2147483648 … 2147483647) here to serve as the
starting value or the reference value for controlling the switching output.
Default setting: -2147483648
Upper limit
The upper limit value can be defined here. If the counter reading lies
outside of the defined range, a limiting value signal is generated – this is
available as a status bit in the process image.
Enter a value (-2147483648 … 2147483647) here to serve as the
starting value or the reference value for controlling the switching output.
Default setting: 2147483647
Lower limit value status The status of the lower limit value is indicated in this field.
Default setting: inactive
Upper limit value status The status of the upper limit value is indicated in this field.
Default setting: active
Wire break
The wire break detection status is indicated in this field.
Default setting: active
Cam detected
The cam detection status is indicated in this field.
Default setting: inactive
Gate time
Enter a value for the gate time here:
1 ms
10 ms
100 ms
1000 ms*
10000 ms
Preset value
Define a preset value here that should be used as the current counter
value when an assigned input signal is detected.
0*
This field is only displayed if you have selected "Incremental encoder"
as the encoder in the
Counter function
field.