WAGO-SPEEDWAY 767
Parameterizing
73
767-5201 TTL Incremental/SSI Encoder
Manual
Version 1.1.0
Table 43: Overview of adjustable parameters for the digital outputs
Parameter
Description:
Actuator restart mode
Set the restart behavior of an enabled output if the output has been
disabled due to the "Overtemperature" diagnosis. You have the
following options:
- Delayed*
After the time set has elapsed ("Restart delay, actuator"), the output is
switched on again automatically.
- Diagnostic acknowledge
The output is only switched on after acknowledging the diagnostic
message. Acknowledge the diagnostic message from the higher-level
control unit or PLC. The respective coupler manual specifies which
fieldbus couplers this functionality supports.
Note about diagnostic acknowledgement
When using fieldbus couplers that do not support
diagnostic acknowledgement, disabled outputs may
remain OFF.
Restart delay actuator
Time in 100 ms intervals, after which a disabled output is switched on
again in case of error.
You must deactivate the checkbox under "Restart mode, actuator" (0).
Default setting: 10
Note
If you set the time of the "Restart delay, actuator"
parameter to 0 ms, the I/O LED appears yellow instead of
red if a short circuit or overload appears due to the short
restart interval (see Section "Diagnostics").
Overtemperature
When the checkbox is selected, there is an overtemperature on the
respective channel (only enabled when the actuator output is switched
on).
* Factory default setting
**
The last value is the value output at the contact prior to the occurrence of the corresponding
error. For example, this can be a process value or "manual operation value".