7.3.2
SSI Encoder Parameters
If you have selected the SSI encoder as the counter function, you can parameterize
as follows:
Table 40: Overview of adjustable parameters for the SSI encoder
Parameter
Description:
Data length
(single-turn data length)
Enter the number of the single-turn bits for the connected encoder here.
8 … 24 bits
Default setting: 13
Multiturn data length
(multi-turn data length)
Enter the data length of the speed of the multi-turn bit for the connected
encoder here.
0 … 24 bits
Default setting: 12
Single turn examination Select here, if only the rotational angle of the encoder should be output.
The speed will be thereby hidden.
Checkbox unselected:*
Speed is output
Checkbox selected:
Speed is not output
Clock rates
Select the bus speed for the SSI bus here. You have the following
options:
6.25 kHz*
125 kHz
250 kHz
500 kHz
1 MHz
2 MHz
Parity
In this box, select the parity setting. You have the following options:
- No*
- Even
- Odd
Encoding format
Select the code that corresponds to the connected SSI encoder:
- Binary*