WAGO-I/O-SYSTEM 750
Diagnostics 113
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
9.7
Connection Errors
In the event of an error connecting to a WBM page, "wbm error" is displayed
instead of any valid data.
Connection errors may occur due to the following factors:
•
The physical ETHERNET connection to the device has been interrupted. In
this case, a PROFINET IO diagnostic message should appear. There may be
a failure of the entire device.
•
The IP connection has been interrupted. Causes may include:
-
Reparameterization of the IP address of the device
-
Failure of the PC network card
•
The maximum number of connections (3) to the WBM page has been
exceeded
Pos : 67 /All e Seri en (Allgemei ne Module)/Ü berschrif ten f ür alle Serien/Diag nos e, Ser vice/Diag nos e - Ü berschrif t 1 @ 4\ mod_1240831069471_21. doc x @ 31372 @ 1 @ 1
10
Diagnostics
Pos : 68 /Serie 750 ( WAGO-I/ O-SYST EM)/Di agnose/Fel dbus koppl er/-contr oller/ PROF INET-Di agnose/Diagnos emöglic hkei ten PROF INET - Ei nleit ung @ 15\ mod_1366792603400_21. doc x @ 117850 @ @ 1
In addition to diagnostics via the WBM (see previous chapter "Web-based
Management"), there are two other options for diagnostics for the fieldbus
coupler.
The listed diagnostic options are described below:
•
LED signaling
for onsite diagnostics
(see chapter "LED Signaling")
•
PROFINET IO diagnostics
by reading the diagnostic data sets (records)
(see chapter "PROFINET IO Diagnostics")