WAGO-I/O-SYSTEM 750
Commissioning 101
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
8.6.1.4
Response to PROFINET IO failure
Table 43: Parameterization DAP – Attribute Response to PROFINET IO failure
Attribute Name
Attribute Value
Description
Response to
PROFINET IO failure
Output image is
stored
For all output submodules parameterized
"according to device settings" (default), the output
data last valid before the fault remains valid.
Substitute values
are switched
The substitute values parameterized on the part of
the output submodules are output.
Output image is
cleared
For all output submodules parameterized
"according to device settings" (default), the output
data is set to zero.
8.6.1.5
Response to K-Bus failure
Table 44: Parameterization DAP – Attribute Response to K-Bus failure
Attribute Name
Attribute Value
Description
Response to K-Bus
failure
PROFINET IO
communication is
stopped
Any existing IO controller application relationships
(IOAR) are terminated.
Input image gets
invalid
Existing IO controller application relationships
(IOAR) are not terminated. However, the process
data qualifiers of all provider (IOPS) and consumer
data (IOCS) are set to the "BAD" status.
8.6.1.6
Activation of the integrated Webserver
Table 45: Parameterization DAP – Attribute Webserver
Attribute Name
Attribute Value
Description
Webserver
(TCP Port 80)
0
(false)
TCP/UDP port 80 is disabled.
The web server is inaccessible.
1 (true)
TCP/UDP port 80 is enabled.
The web server is accessible.
The web server of the fieldbus coupler is disabled by default and can only be
enabled by the DAP parameterization data set.
Activity is terminated after any hardware or software reset of the fieldbus coupler.
8.6.1.7
Activation of Firmware Updates
Table 46: Parameterization DAP – Attribute WAGO-Service (TCP Port 6626)
Attribute Name
Attribute Value
Description
WAGO Service
(TCP Port 6626)
0 (false)
WAGO TCP service port 6626 is disabled. The
device software cannot be updated by a firmware
update via ETHERNET.
1
(true)
WAGO TCP service port 6626 is enabled. The
device software can be updated by a firmware
update via ETHERNET.
The WAGO service port of the fieldbus coupler is enabled by default and can only
be disabled by the DAP parameterization data set.