TITANUS
SUPER·SENS
®
Pipe
Design
TSS_04_A-en-e
Data: 02/09
4 –
27
Double U-pipe system triggering thresholds
per pipe system
Number of apertures
4
8
12
16
1
blocked aperture
II
I —
—
13F
14
2
blocked apertures
III
I
I
—
4
blocked apertures
{
14F
15
III
II
I
6
blocked apertures
{
{
III
II
8
blocked apertures
{
{
III
III
… has/have been detected at setting level x
Example
If blockage of
2
aspiration apertures of a total of
8
aspiration apertures is
intended to be detected, the air flow monitoring setting switch should be
set to
level I.
Air flow monitoring level I, II or III should be set in any case for project
planning in conformity with EN 54-20.
14
— not possible
15
{
not purposeful
INSTRUCTION