Commissioning
TITANUS
SUPER·SENS
®
7
– 8
Data: 02/09
TSS_07_A-en-e
Fig. 7.4: Operational check of
TITANUS
®
Connect the test pipe.
Connect the pressure measuring hose to the adapter connector
B.
Connect the 4-pole plug of the adapter to the digital manometer
and switch it on.
7.5.2
Operational
Check
The operational check can be effected with or without a digital manome-
ter. In the following the complete check is described. If during the opera-
tional check the values vary from those given in the following TITANUS
®
or its air flow sensor are damaged.
1. Close all air sampling points of the test pipe by means of adhesive
tape.
After a short initiation period (approximately 20 s) the depression
generated in TITANUS
®
is to be between 155 Pa und 190 Pa.
2. Unblock at each test pipe the 7.0 mm and the 4.2 mm-air sampling
point.
Press the Init-button (S3) on the base board and close the housing
lid. The operating-LED flashes and the fault-LED has to extinguish.