Installation
TITANUS
SUPER·SENS
®
5
– 26
Data: 02/09
TSS_05_B-en-e
5.9
TITANUS
®
in the network system
As an option several TITANUS
®
can be connected to form a network.
This network system permits the operator to monitor the states of all con-
nected TITANUS
®
. The courses of the smoke level, the air flow values or
the alarm and fault states e.g. are transmitted via the bus system.
For the operation of TITANUS
®
in the network a special PC-software and
a network board are necessary which are both not included.
5.9.1 Installation network board in TITANUS
®
Fig. 5.20: Installation network board in
TITANUS
®
In order to install the network board open the air sampling smoke detec-
tion system according to chapter 5.2. Then, follow the steps below:
Lock the three plastic distance pins in the prepared drill holes of
the TITANUS
®
-base board
.
Attach the 10-pole connection cable to plug X5 (SCI) of the
TITANUS
®
-base board.
Lock the network board in the three plastic distance pins.
Attach the 10-pole connection cable with plug X2 of the network
board.